Comparing Evaporator Inlet/Outlet
Temperatures
The temperatures of the suction lines entering and
leaving the evaporator alone cannot diagnose an ice
machine. However, comparing these temperatures
during the freeze cycle, along with using Manitowoc’s
Refrigeration System Operational Analysis Table, can help
diagnose an ice machine malfunction.
The actual temperatures entering and leaving the
evaporator vary by model, and change throughout
the freeze cycle. This makes documenting the “normal”
inlet and outlet temperature readings difficult. The key
to the diagnosis lies in the difference between the two
temperatures five minutes into the freeze cycle. These
temperatures must be within 7°F (4°C) of each other.
Use this procedure to document freeze cycle inlet and
outlet temperatures.
1. Use a quality temperature meter, capable of taking
temperature readings on curved copper lines.
2. Attach the temperature meter sensing device to the
copper lines entering and leaving the evaporator.
Important
Do not simply insert the sensing device under the
insulation. It must be attached to and reading the
actual temperature of the copper line.
3. Wait five minutes into the freeze cycle.
4. Record the temperatures below and determine the
difference between them.
___________
___________
___________
Inlet
Temperature
Difference must be within
7°F (4°C) at 5 minutes into
the freeze cycle
Outlet
Temperature
5. Use this with other information gathered on the
Refrigeration System Operational Analysis Table to
determine the ice machine malfunction.
Summary of Contents for STH042 4/16
Page 2: ......
Page 14: ...14 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...42 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 56: ...56 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 98: ...98 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 126: ...126 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 136: ...136 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Page 137: ...Part Number STH042 4 16 137 U310 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Page 138: ...138 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Page 139: ...Part Number STH042 4 16 139 U310 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Page 144: ...144 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 145: ......