Ice Making Sequence of Operation
NOTE: To date there are two main revisions to the
sequence of operation.
1. Software version 2.58 and higher have a 25 second
water pump delay in the freeze cycle.
2. Control boards with a J4 terminal can utilize a
thermistor to control when the water pump delay
occurs in the freeze cycle.
WITH WATER TROUGH THERMISTOR
The following sequence occurs in the freeze cycle:
• When the temperature of the water reaches 34° F the
water pump de-energizes for 25 seconds,
then re energizes.
• When the water pump restarts the water inlet
solenoid energizes for 7 seconds.
WITHOUT WATER TROUGH THERMISTOR
The following sequence occurs in the freeze cycle:
• At 3.75 minutes the water pump de-energizes for 25
seconds, then re-energizes.
• When the water pump restarts the water inlet
solenoid energizes for 7 seconds.
Summary of Contents for STH042 4/16
Page 2: ......
Page 14: ...14 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...42 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 56: ...56 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 98: ...98 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 126: ...126 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 136: ...136 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Page 137: ...Part Number STH042 4 16 137 U310 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Page 138: ...138 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Page 139: ...Part Number STH042 4 16 139 U310 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Page 144: ...144 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 145: ......