S12800 Routing Switch Installa
tion Manual V1.0
Maipu Confidential & Proprietary Information
Page 26
Before installing the pallet, confirm whether the load-bearing capability of the used pallet
meets the weight requirement of S12800 chassis and inside inserted cards. For the
weights of the components, refer to
Appendix A Entire Device and Common Module
Ensure that the distance between the pallet and the cabinet bottom is 2U and the three
holes on the square hole bar are 1U, as shown in Figure 3-3.
1U is 44.45mm. Here, U is short for Rack Unit.
Figure 3-3 The diagram of the pallet installation height
1. Cabinet column
2. Load-bearing pallet
The following takes the 19-inch standard cabinet as an example to describe how to install the
pallet.
The steps for installing the pallet are as follows:
Step 1:
Confirm the installation location of the pallet on the cabinet and use the marker
to mark the installation hole position.
The space height above the pallet should be larger than the height of the installed device
chassis and there is enough margin (1U margin is recommended).
To ensure the stability of the cabinet, try to install the heavy and high device at the
bottom of the cabinet.