ULTRA By Maguire
- Ultra Low Energy Dryer
BLA - Blower Level Adjustment
format:
xxxxx
(Hz)
function(s):
Blower drive frequency when the heating hopper level is at or below that set by the BZL
parameter.
Note: this parameter is only visible on units equipped with a VFD.
BHT - Blower Heat Throttle
format:
xxxxx
(%)
function(s):
After a vacuum chamber fill, when the heater powers back up, it will run at this
percentage of the duty cycle it ran at the end of the previous vacuum cycle if the heating
hopper level is below that established by the BZL parameter. This is to mitigate
temperature runaways caused by different airflows (caused by different pressure drops
across the heating hopper).
Note: this parameter is only visible on units equipped with
a VFD and a heating hopper level sensor.
BMW - Blower Maximum Wattage
format:
xxxxx
(watts)
function(s):
The amount of power the blower consumes when running at full speed. This value is
used in energy consumption calculations.
BDT - Blower Delay Time
format:
xxxxx
(seconds)
function(s):
The amount of time between the completion of vacuum chamber re-filling and the blower
powering-up.