WEB SERVER
www.maxcessintl.com
DLCA NET-ECAT
MI 850A365 1
Page 67 of 72
10.1
Tension calibration from web pages
To calibrate tension from the web pages, edit the parameters
below in the proper tension zone before performing the
calibration commands.
10.1.1
Precision calibration from web pages
For Precision Calibrate enter these parameters:
Load Cell Excitation voltage (on Hardware web page)
Which Sensor Inputs Used (on Hardware web page)
Maximum Tension
Calibration Tension
Decimal Point Position
Procedure
1.
Unload the load cells.
2.
Click on the link to "Zero Calibrate Tension Zone x".
Wait for the calibration to complete.
3.
Apply the calibration weight to the temporary web.
4.
Click on the link to "Precision Calibrate Tension Zone x".
Wait for the calibration to complete.
5.
The DCLA NET-ECAT will return either that the calibration
is complete or return an error message.
10.1.2
Weightless calibration from web pages
For Weightless Calibrate enter these parameters:
Load Cell Excitation voltage (on Hardware web page)
Which Sensor Inputs Used (on Hardware web page)
Load Cell Sensitivity
Load Cell Rating
Maximum Tension
Web Wrap Angle
Angle from Force Direction
Decimal Point Position
Procedure
1.
Unload the load cells.
2.
Click on the link to "Zero Calibrate Tension Zone x".
Wait for the calibration to complete.
3.
Click on the link to "Weightless Calibrate Tension Zone x".
4.
The DCLA NET-ECAT will return that the calibration is
complete or return an error message.