CALIBRATE TENSION USING MENU
www.maxcessintl.com
DLCA NET-ECAT
MI 850A365 1
Page 28 of 72
Precision calibration continued
Use [+] and/or [-] to go to CAL1.1 or CAL2.1. Press [Enter] to enter
the sub-menu.
Display now shows C11.1 or C21.1. Unload the load cells roller and
press [Enter]. The DLCA NET-ECAT will now zero out the idler roll
weight and show a wait display. After zeroing, the DLCA NET-ECAT
will automatically increment to the next parameter.
Display now shows C11.2 or C21.2. Press [Enter] and select the
decimal point position for tension. Press and hold [Enter] for two
seconds (until the display starts flashing) to store the decimal point
position. Range {000000, 000000., 00000.0, 0000.00, 000.000,
00.0000, 0.00000}.
Display now shows C11.3 or C21.3. Press [Enter] and enter the
maximum tension. Press and hold [Enter] for two seconds (until the
display starts flashing) to store the parameter. This value scales the
output. The output will be at 10 volts or 20 mA when the measured
tension matches this value. The maximum output voltage or current
is set by the sub-menus OP1, OP2, OP3, and OP4.
Display now shows C11.4 or C21.4. Press [Enter] and enter the
calibration tension that will be applied to the load cell roller. Press
and hold [Enter] for two seconds (until the display starts flashing) to
store the parameter. Range {0, 999000}.