PARAMETERS
www.maxcessintl.com
DLCA NET-ECAT
MI 850A365 1
Page 41 of 72
7.5
Analog output scaling
Each analog output’s output values for zero tension and maximum tension can be set by the
following parameters. The default for the 0 to 20mA outputs is 0 and 20mA. Use these
parameters to scale the 0 to 20mA output to be 4 to 20mA.
Parameter
Description
Units
Default
Range
Output 1
OP1.1
Sets the 0 to 10V output voltage
when the tension is zero.
0.01 volts
00.00
{00.00,
10.00}
OP1.2
Sets the 0 to 10V output voltage
when the tension is equal to
maximum tension.
0.01 volts
10.00
{00.00,
10.00}
OP1.3
Sets the 0 to 20mA output current
when the tension is zero.
0.01 mA
04.00
{00.00,
20.00}
OP1.4
Sets the 0 to 20mA output current
when the tension is equal to
maximum tension.
0.01 mA
20.00
{00.00,
20.00}
Output 2
OP2.1
Sets the 0 to 10V output voltage
when the tension is zero.
0.01 volts
00.00
{00.00,
10.00}
OP2.2
Sets the 0 to 10V output voltage
when the tension is equal to
maximum tension.
0.01 volts
10.00
{00.00,
10.00}
OP2.3
Sets the 0 to 20mA output current
when the tension is zero.
0.01 mA
04.00
{00.00,
20.00}
OP2.4
Sets the 0 to 20mA output current
when the tension is equal to
maximum tension.
0.01 mA
20.00
{00.00,
20.00}
Output 3
OP3.1
Sets the 0 to 10V output voltage
when the tension is zero.
0.01 volts
00.00
{00.00,
10.00}
OP3.2
Sets the 0 to 10V output voltage
when the tension is equal to
maximum tension.
0.01 volts
10.00
{00.00,
10.00}
OP3.3
Sets the 0 to 20mA output current
when the tension is zero.
0.01 mA
04.00
{00.00,
20.00}
OP3.4
Sets the 0 to 20mA output current
when the tension is equal to
maximum tension.
0.01 mA
20.00
{00.00,
20.00}
Meter Output
OP4.1
Sets the 0 to 1 meter output 1
current when the tension is zero.
0.01 mA
00.00
{00.00,
01.00}