PARAMETERS
www.maxcessintl.com
DLCA NET-ECAT
MI 850A365 1
Page 43 of 72
CO.33
Sets the 0 to 20mA output to 0%.
Change the value until the meter reads 0.00 mA.
{0, 9999}
CO.34
Sets the 0 to 20mA output to 100%.
Change the value until the meter reads 20.00 mA,
{0, 9999}
Meter Output
CO.41
Sets the meter output 1 to 0%.
Change the value until the meter reads 0.00 mA.
{0, 9999}
CO.42
Sets the meter output 1 to 100%.
Change the value until the meter reads 1.00 mA.
{0, 9999}
CO.43
Sets the meter output 2 to 0%.
Change the value until the meter reads 0.00 mA
{0, 9999}
CO.44
Sets the meter output 2 to 100%.
Change the value until the meter reads 1.00 mA
{0, 9999}