23
48-635 E3 Modulevel
®
Displacer Level Transmitter
Display
Action
Comment
14
Trim 20
xxxx
Fine tune 20 mA point
Adjust setting (Trim 4 value – 4095) to output exactly 20.0 mA
15
Loop Tst
xx.x mA
Enter a mA output value
to test loop
16
Capture
4.00 mA
Pressing
in Data Entry
Mode captures current sg
output as 4.00 mA Set Point
Current SpecGrav set as 4 mA point. Submerge displacer in
lowest SG liquid. Press
and
to “capture” this SG as your
4 mA density.
17
Capture
20.00 mA
In Data Entry Mode, can
adjust loop value to corre-
spond to current sg output
for setting 20.00 mA Set
Point
(8.00
≤
loop value
≤
20.00 mA)
Set second SpecGrav point between 8.00 mA and 20.00 mA.
Submerge displacer in higher SG liquid. Press
and
to
“capture” this SG as your upper loop value between 8.00 and
20.00 mA.
18
New Pass
xxx
Enter new password (0 – 255) Displays encrypted value of present password
Default value = 0
19
Language
(select)
Select from English, Spanish,
French, German
Language choice for LCD display
20
E3 ModHT
Ver 1.0
Transmitter Display
Product identification
Firmware version
21
DispFact
(select)
Select “Yes” to display factory
parameter menu as below
Selecting “No” takes you back to beginning of menu
22
History
(current status)
Diagnostic Display to view
present status and recent
exceptions
Press
to view recent exceptions, up to ten events
23
Run Time
xxxx.x h
Diagnostic Display showing
elapsed time since power on
or History Reset
24
History
Reset
Factory only
25
MeasType
(select)
Factory set
Level, IfcLevel, or Density
26
Model
(select)
Factory set
E3A, E3B, E3C, E3D, E3E, E3F
27
SpringSG
(select)
Factory set
Model specific
28
SprgRate
x.x
Factory set
Model specific
29
SprgMatl
Factory set
Model specific
30
TempLimt
xxx F
Factory set
Model specific—maximum process temperature for which unit is
suitable
31
Length
xx.xx lu
Factory set
Model specific—length of measuring range
32
Diameter
x.xxx in
Factory set
Model specific—outside diameter of displacer
33
Weight
x.xx oz
Factory set
Model specific—weight of displacer and stem assembly
34
CalSelct
(select)
Select Factory or User
Calibration
Selects Calibration Parameters used to calculate the
measured PV
35a
Factory
Cal Menu
Press
to display the
Factory Calibration sub-menu
CalSelct = Factory
Submenu on page 24
2.6.5.3
Measurement Type: Density (cont.)