22
48-635 E3 Modulevel
®
Displacer Level Transmitter
2.6.5.3
Measurement Type: Density
Display
Action
Comment
1
*Status*
*SG *
*% Out *
* Loop *
Transmitter Display
2
SpecGrav
x.xx sg
Transmitter Display
(Alternate Home Menu)
3
% Output
xx.x %
Transmitter Display
(Alternate Home Menu)
4
Loop
xx.xx mA
Transmitter Display
(Alternate Home Menu)
5
OperTemp
xxx F
Enter the Process Operating
Temperature
Adjusts factory calibration for actual temperature
(limited by maximum temperature rating of model)
6
Set 4mA
xx.xx sg
Enter the SpecGrav value for
4 mA set point
Assigns specific gravity value to 4 mA loop value
7
Set 20mA
xx.xx sg
Enter the SpecGrav value for
20 mA set point
Assigns specific gravity value to 20 mA loop value
8
Damping
xx s
Enter time constant of
desired damping
0 to 45 sec
9
Fault
(select)
Select loop current value in
presence of a fault
Select from 3.6 mA, 22 mA or Hold
10
Poll Adr
xx
Enter HART polling address
number
If multidrop is not in use, poll address must = 0
11
Loop Mode
(select)
Enable/Disable
Loop Current Mode
If enabled, loop current follows the PV; If disabled, loop current is
fixed (i.e., multidrop mode).
12
Trim SG
x.xx sg
Enter value to adjust SG
reading
Fine tune SpecGrav reading
13
Trim 4
xxxx
Fine tune 4 mA point
Adjust setting (0 – Trim 20 value) to output exactly 4.0 mA
2.6.5.2
Measurement Type: Interface Level (cont.):
Factory (display only) or User Calibration sub-menu
Display
Action
Comment
1
LVDT%
xx.xx %
Diagnostic display
2
DrySensr
xx.xx %
Enter or capture sensor
output for Dry Sensor
Press
and
simultaneously to capture current
sensor output
3
SnrCalLo
xx.xx %
Enter or capture sensor
output for Low Cal Point
Press
and
simultaneously to capture current
sensor output
4
LvlCalLo
xx.xx lu
Enter IfcLevel value corre-
sponding to SnrCalLo
5
Set 4mA
xx.xx lu
Enter the IfcLevel value for
4 mA set point
Assigns Level value to 4 mA loop value (User Cal menu only)
6
SnrCalHi
xx.xx %
Enter or capture sensor
output for High Cal Point
Press
and
simultaneously
to capture current sensor output
7
LvlCalHi
xx.xx lu
Enter IfcLevel value corre-
sponding to SnrCalHI
8
Set 20 mA
xx.xx lu
Enter the IfcLevel value for
20 mA set point
Assigns Level value to 20 mA loop value (User Cal menu only)
9
Escape
Press
to exit Calibration
sub-menu; Returns to
Factory Menu