17
48-635 E3 Modulevel
®
Displacer Level Transmitter
The numbers are not shown on the display. They are pro-
vided as a reference.
The third column provides the actions to take when
configuring the transmitter. Additional information or an
explanation of an action is given in the fourth column.
Configuration tips:
If “Calselct” is Factory, Factory Cal Menu is available for
viewing only. Only calibration parameters in User Cal
Menu can be changed by the user.
To capture the current sensor value, press
and
simultaneously.
PV = Primary Variable = Level or Interface Level or Density
(depending on Measurement Type).
2.6.5.1
Measurement Type: Level
Display
Action
Comment
1
*Status*
*Level *
*% Out *
* Loop *
Transmitter Display
2
Level
xx.xx lu
Transmitter Display
(Alternate Home Menu)
3
% Output
xx.x %
Transmitter Display
(Alternate Home Menu)
4
Loop
xx.xx mA
Transmitter Display
(Alternate Home Menu)
5
LvlUnits
(select)
Select the level units
of measure
Select cm, inches, feet, meters
6
Proc SG
x.xxx sg
Enter the specific gravity of the
process liquid at operating temp.
Adjusts factory calibration for actual specific gravity
(limited by SG range of spring)
7
OperTemp
xxx F
Enter the Process Operating
Temperature
Adjusts factory calibration for actual temperature
(limited by maximum temperature rating of model)
8
Set 4mA
xx.xx lu
Enter the level value for 4 mA
set point
Specify level at 4 mA
9
Set 20mA
xx.xx lu
Enter the level value for
20 mA set point
Specify level at 20 mA
10
Lvl Ofst
xx.xx lu
Enter desired output when
level is at the calibrated zero
reference
Minimum offset = -(displacer length)
Zero reference is typically bottom of displacer or centerline of
bottom-side process connection.
11
Damping
xx s
Enter time constant of
desired damping
0 to 45 sec
12
Fault
(select)
Select loop current value in
presence of a fault
Select from 3.6 mA, 22 mA or Hold
13
Poll Adr
xx
Enter HART polling address
number
If multidrop is not in use, poll address must = 0
14
Loop Mode
(select)
Enable/Disable
Loop Current Mode
If enabled, loop current follows the PV; If disabled, loop current is
fixed (i.e., multidrop mode).