6 (E)
4. B&R: Operations to be performed using
Automation Studio
The description in this section uses the B&R “Automation Studio V4.2.3.159” as the
development environment.
This description also uses the B&R X20CP3585(CPU), X20IF10E1-1 (PROFINET RT
master as the network element. The network is constructed locally, and the IP address of
each element is set as a static IP address as shown in the table below.
Table 4-1 IP address settings of various equipment used in the B&R Automation Studio
introduction
Equipment name
IP address
Subnet mask value
Development computer
192.168.0.1
255.255.255.0
X20CP3585 CPU
192.168.0.11
X20IF10E1-1 PROFINET RT master
192.168.0.20
X20BC00E3 PROFINET RT slave
192.168.0.101
4.1. Importing the GSDML file
1.
Start up Automation Studio, and select “Tools”
→
“Import DTM Device…” from
the menu.
After that, a file-selection window will be displayed.
Fig 4-1
Automation Studio -- Importing the GSDML file -- No.1
2.
Select the GSDML file (GSDML-V2.25-BR-X20BC00E3-20160415.xml)
downloaded in section 3 above.
3.
A window will open asking whether to execute the DTM catalog update. Click
“Yes”.
Fig 4-2