background image

5.  COMPONENT IDENTIFICATIONS

T6

T7

T8

DB

DA

DG FG SLD

A

F G

B

C

D

E

H

NAME

FUNCTIONS

A

Power terminal block

For power input

B

Network terminal block

For wiring to CC-Link

SETTING

BAUD RATE

C

Baud rate setting

0
1
2
3
4
Other than 0 – 4

156 kbps (factory default)
625 kbps
2.5 Mbps
5 Mbps
10 Mbps
Not valid; L ERR. turns on as a transmission error.

D

Station No. setting

Ver. 1.10: Selectable within 1 – 61.  (factory set to: 00)
Ver. 2.00: Selectable within 1 – 64.  (factory set to: 00)

ID (color)

FUNCTIONS

E

Status indicator LED

L RUN (red)

ON: 
Blinking : 
OFF: 

Normal communication
Transmission data error
Communication down (time-out error)

L ERR. (red)

ON : 
Blinking : 
OFF: 

Transmission data error
Transmission data error
Normal transmission

SD (red)

ON when transmitting

RD (red)

ON when receiving

ID (color)

FUNCTIONS

F

Power LED

PWR (green)

ON: 
Blinking, high speed: 
Blinking, low speed: 

Abnormality
CC-Link Ver. 1.10
CC-Link Ver. 2.00
Master Version 2.00 with long ON time
Master Version 1.10 with long OFF time

G

Configurator jack

2.5 dia. miniature jack; RS-232-C level

H

Specifications

Display(s) serial No., model No., etc.

6.  INSTALLATION

 

DIN RAIL MOUNTING

Set the body so that its DIN rail adaptor is at the bottom.  Pull down the DIN rail 
adaptor.
Position the upper hook at the rear side on the DIN rail and push in the lower.  Push 
back the DIN rail adaptor.

 

WALL MOUNTING

Set the body so that its DIN rail adaptor is at the bottom.  Pull down the DIN rail 
adaptor.
Refer to “EXTERNAL DIMENSIONS.”

DIN Rail Adaptor

DIN Rail

35mm wide

R1C-GH

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5956  Rev.11  P. 5 / 13

Summary of Contents for R1C-GH

Page 1: ...9 3 WIRING DIAGRAM 9 10 SELECTING CC LINK VERSION 9 11 DATA LIST 10 11 1 REMOTE I O 10 11 2 ASSIGNING REMOTE REGISTERS 10 11 3 A D CONVERSION 10 12 PARAMETERS SETTING BY PLC PROGRAM 11 12 1 GENERAL DE...

Page 2: ...qualified personnel PACKAGE INCLUDES Thermocouple DC input module body CJC sensor 1 Terminating resistor 110 0 5 W 1 MODEL NO Confirm Model No marking on the product to be exactly what you ordered IN...

Page 3: ...the module inside proper housing with sufficient ventila tion Do not install the module where it is subjected to continuous vibration Do not subject the module to physical impact Environmental tempera...

Page 4: ...0 0 5 0 to 600 L 200 to 900 0 3 0 to 900 P Platinel II 0 to 1395 0 5 0 to 1395 CJC error 3 C at 20 C 10 C Number of inputs 16 Isolation Input to CC Link FG to power Required nodes CC Link Ver 1 10 4 R...

Page 5: ...when transmitting RD red ON when receiving ID color FUNCTIONS F Power LED PWR green ON Blinking high speed Blinking low speed Abnormality CC Link Ver 1 10 CC Link Ver 2 00 Master Version 2 00 with lo...

Page 6: ...or 7 1 EXTERNAL DIMENSIONS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35 104 4 09 10 39 105 4 13 14 55 163 6 42 36 M3 INPUT TERMINALS 165 6 50 175...

Page 7: ...model R1CON or consult M System to confirm the firmware version Caution FG1 terminal is NOT a protective conductor terminal 9 8 7 6 5 4 3 2 1 10 12 11 13 15 14 16 17 18 20 19 21 22 23 24 25 27 26 28 2...

Page 8: ...8 SW401 SW408 ch 9 ch 16 Set to position 1 Attenuation OFF SW311 ch 1 ch 8 SW411 ch 9 ch 16 OFF Voltage input 0 8V or less SW301 SW308 ch 1 ch 8 SW401 SW408 ch 9 ch 16 Set to position 1 Attenuation OF...

Page 9: ...the wires 6 DO NOT DAMAGE the insulation tube of wires 9 3 WIRING DIAGRAM Connect the R1C to the Master Unit as shown below DA DB DG SLD FG MASTER UNIT DA DB DG SLD FG R1C DA DB DG SLD FG I O UNIT TER...

Page 10: ...er RWrn 0 Ch 1 digital output 0 RWrn 1 Ch 2 digital output 0 RWrn 2 Ch 3 digital output 0 RWrn 3 Ch 4 digital output 0 RWrn 4 Ch 5 digital output 0 RWrn 5 Ch 6 digital output 0 RWrn 6 Ch 7 digital out...

Page 11: ...ration specification when the CPU is down Reserved station specification X002F M0 M1 PLS M0 SET M1 RST M1 MOV D0 MOV D1 MOV D2 MOV D3 MOV D4 MOV D5 MOV D6 MOV D7 MOV D8 MOV D9 MOV D10 D11 MOV D13 D MO...

Page 12: ...ndicator blinking or ON Consult the users manual for the Master Unit Is the RUN indicator on the PLC CPU blinking or OFF Consult the users manual for the CPU Is the RUN indicator on the Master Unit OF...

Page 13: ...ocedure is explained below CALIBRATION Warm up the module for at least 10 minutes Apply 0 25 50 75 and 100 input signal Check that the A D conversion data for the respective input signal remains withi...

Reviews: