2.  GENERAL DESCRIPTION

The model R1C-GH, Thermocouple & DC Input Module, is used as remote device for CC-Link.
Model number and suffix codes are designated as follows:

R1C−GH2T−x

MODEL

POWER INPUT

 M2 

: 100 – 240V AC

   R 

: 24V DC

FIELD TERMINAL TYPE

 T 

: M3 screw terminals

I

/

O TYPE

GH2 

: Thermocouple or DC input, 16 points

The R1C accepts 16 points of thermocouple and/or DC input signals.  It converts analog inputs (0 – 100%) 
proportionally into 16-bit signed binary signals.
CC-Link Version 1.10 and 2.00 can be switched at the startup.
This instruction manual explains hardware specifications, component identification, and wiring instruc-
tions, etc.

3.  POINTS OF CAUTION

 

GENERAL PRECAUTIONS

• Before you remove the module, turn off the power supply and input signal for safety.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the air, install the module inside proper housing with sufficient ventila-

tion.

• Do not install the module where it is subjected to continuous vibration.  Do not subject the module to physical impact.
• Environmental temperature must be within -5 to +60°C (23 to 140°F) with relative humidity within 30 to 90% RH in order 

to ensure adequate life span and operation.

• Be sure that the ventilation slits are not covered with cables, etc.

 

WIRING

• Wrong connection may damage the module.
• Do not connect cables to moving parts or pull them tightly.
• Do not install cables close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present.  Do not install them in the same duct.

 

AND ....

• The module is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfy-

ing complete performance described in the data sheet.

R1C-GH

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5956  Rev.11  P. 3 / 13

Summary of Contents for R1C-GH

Page 1: ...9 3 WIRING DIAGRAM 9 10 SELECTING CC LINK VERSION 9 11 DATA LIST 10 11 1 REMOTE I O 10 11 2 ASSIGNING REMOTE REGISTERS 10 11 3 A D CONVERSION 10 12 PARAMETERS SETTING BY PLC PROGRAM 11 12 1 GENERAL DE...

Page 2: ...qualified personnel PACKAGE INCLUDES Thermocouple DC input module body CJC sensor 1 Terminating resistor 110 0 5 W 1 MODEL NO Confirm Model No marking on the product to be exactly what you ordered IN...

Page 3: ...the module inside proper housing with sufficient ventila tion Do not install the module where it is subjected to continuous vibration Do not subject the module to physical impact Environmental tempera...

Page 4: ...0 0 5 0 to 600 L 200 to 900 0 3 0 to 900 P Platinel II 0 to 1395 0 5 0 to 1395 CJC error 3 C at 20 C 10 C Number of inputs 16 Isolation Input to CC Link FG to power Required nodes CC Link Ver 1 10 4 R...

Page 5: ...when transmitting RD red ON when receiving ID color FUNCTIONS F Power LED PWR green ON Blinking high speed Blinking low speed Abnormality CC Link Ver 1 10 CC Link Ver 2 00 Master Version 2 00 with lo...

Page 6: ...or 7 1 EXTERNAL DIMENSIONS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35 104 4 09 10 39 105 4 13 14 55 163 6 42 36 M3 INPUT TERMINALS 165 6 50 175...

Page 7: ...model R1CON or consult M System to confirm the firmware version Caution FG1 terminal is NOT a protective conductor terminal 9 8 7 6 5 4 3 2 1 10 12 11 13 15 14 16 17 18 20 19 21 22 23 24 25 27 26 28 2...

Page 8: ...8 SW401 SW408 ch 9 ch 16 Set to position 1 Attenuation OFF SW311 ch 1 ch 8 SW411 ch 9 ch 16 OFF Voltage input 0 8V or less SW301 SW308 ch 1 ch 8 SW401 SW408 ch 9 ch 16 Set to position 1 Attenuation OF...

Page 9: ...the wires 6 DO NOT DAMAGE the insulation tube of wires 9 3 WIRING DIAGRAM Connect the R1C to the Master Unit as shown below DA DB DG SLD FG MASTER UNIT DA DB DG SLD FG R1C DA DB DG SLD FG I O UNIT TER...

Page 10: ...er RWrn 0 Ch 1 digital output 0 RWrn 1 Ch 2 digital output 0 RWrn 2 Ch 3 digital output 0 RWrn 3 Ch 4 digital output 0 RWrn 4 Ch 5 digital output 0 RWrn 5 Ch 6 digital output 0 RWrn 6 Ch 7 digital out...

Page 11: ...ration specification when the CPU is down Reserved station specification X002F M0 M1 PLS M0 SET M1 RST M1 MOV D0 MOV D1 MOV D2 MOV D3 MOV D4 MOV D5 MOV D6 MOV D7 MOV D8 MOV D9 MOV D10 D11 MOV D13 D MO...

Page 12: ...ndicator blinking or ON Consult the users manual for the Master Unit Is the RUN indicator on the PLC CPU blinking or OFF Consult the users manual for the CPU Is the RUN indicator on the Master Unit OF...

Page 13: ...ocedure is explained below CALIBRATION Warm up the module for at least 10 minutes Apply 0 25 50 75 and 100 input signal Check that the A D conversion data for the respective input signal remains withi...

Reviews: