background image

9.  CONNECTING DATA LINK WIRES

The following explanations apply to the wires connecting the R1C to the Master Unit.

9.1.  TWISTED-PAIR CABLE

The following types of wire are recommended for connecting the R1C to the Master Unit.

  KURAMO ELECTRIC  FANC-SB  0.5 mm

2

 × 3 or equivalent

white

blue

yellow

Sheath

DA

Shielding

Aluminum Tape

DG

Grounding

DB

9.2.  POINTS OF CAUTION IN HANDLING WIRES

DO NOT apply extraordinary forces to the wires as explained in the following:

1) DO NOT SQUEEZE the wires with a sharp-edged tool.
2) DO NOT TWIST the wires extraordinarily.
3) DO NOT PULL the wires extraordinarily tight.
4) DO NOT TRAMPLE on the wires.
5) DO NOT PUT objects onto the wires.
6) DO NOT DAMAGE the insulation tube of wires.

9.3.  WIRING DIAGRAM

Connect the R1C to the Master Unit as shown below.

DA
DB

DG

SLD

FG

MASTER UNIT

DA
DB

DG

SLD

FG

R1C

DA
DB

DG

SLD

FG

I/O UNIT

TERMINATOR

blue

white

yellow

10. SELECTING CC-LINK VERSION

The R1C-GH is usable both for CC-Link Ver. 1.10 and Ver. 2.00.  The contact status of the version selec-
tor input at the moment of the power supplied determines the CC-Link version.  Required node numbers 
depends upon the version No as shown below.  For use with Ver. 2.00, set the cyclic expansion to ‘4’ at the 
Master Unit.

VERSION SELECTOR INPUT

CC-LINK VERSION

REQUIRED NODES

SELECTABLE STATION NO.

ON

Ver. 2.00

1

1 through 64

OFF

Ver. 1.10

4

1 through 61

R1C-GH

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5956  Rev.11  P. 9 / 13

Summary of Contents for R1C-GH

Page 1: ...9 3 WIRING DIAGRAM 9 10 SELECTING CC LINK VERSION 9 11 DATA LIST 10 11 1 REMOTE I O 10 11 2 ASSIGNING REMOTE REGISTERS 10 11 3 A D CONVERSION 10 12 PARAMETERS SETTING BY PLC PROGRAM 11 12 1 GENERAL DE...

Page 2: ...qualified personnel PACKAGE INCLUDES Thermocouple DC input module body CJC sensor 1 Terminating resistor 110 0 5 W 1 MODEL NO Confirm Model No marking on the product to be exactly what you ordered IN...

Page 3: ...the module inside proper housing with sufficient ventila tion Do not install the module where it is subjected to continuous vibration Do not subject the module to physical impact Environmental tempera...

Page 4: ...0 0 5 0 to 600 L 200 to 900 0 3 0 to 900 P Platinel II 0 to 1395 0 5 0 to 1395 CJC error 3 C at 20 C 10 C Number of inputs 16 Isolation Input to CC Link FG to power Required nodes CC Link Ver 1 10 4 R...

Page 5: ...when transmitting RD red ON when receiving ID color FUNCTIONS F Power LED PWR green ON Blinking high speed Blinking low speed Abnormality CC Link Ver 1 10 CC Link Ver 2 00 Master Version 2 00 with lo...

Page 6: ...or 7 1 EXTERNAL DIMENSIONS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35 104 4 09 10 39 105 4 13 14 55 163 6 42 36 M3 INPUT TERMINALS 165 6 50 175...

Page 7: ...model R1CON or consult M System to confirm the firmware version Caution FG1 terminal is NOT a protective conductor terminal 9 8 7 6 5 4 3 2 1 10 12 11 13 15 14 16 17 18 20 19 21 22 23 24 25 27 26 28 2...

Page 8: ...8 SW401 SW408 ch 9 ch 16 Set to position 1 Attenuation OFF SW311 ch 1 ch 8 SW411 ch 9 ch 16 OFF Voltage input 0 8V or less SW301 SW308 ch 1 ch 8 SW401 SW408 ch 9 ch 16 Set to position 1 Attenuation OF...

Page 9: ...the wires 6 DO NOT DAMAGE the insulation tube of wires 9 3 WIRING DIAGRAM Connect the R1C to the Master Unit as shown below DA DB DG SLD FG MASTER UNIT DA DB DG SLD FG R1C DA DB DG SLD FG I O UNIT TER...

Page 10: ...er RWrn 0 Ch 1 digital output 0 RWrn 1 Ch 2 digital output 0 RWrn 2 Ch 3 digital output 0 RWrn 3 Ch 4 digital output 0 RWrn 4 Ch 5 digital output 0 RWrn 5 Ch 6 digital output 0 RWrn 6 Ch 7 digital out...

Page 11: ...ration specification when the CPU is down Reserved station specification X002F M0 M1 PLS M0 SET M1 RST M1 MOV D0 MOV D1 MOV D2 MOV D3 MOV D4 MOV D5 MOV D6 MOV D7 MOV D8 MOV D9 MOV D10 D11 MOV D13 D MO...

Page 12: ...ndicator blinking or ON Consult the users manual for the Master Unit Is the RUN indicator on the PLC CPU blinking or OFF Consult the users manual for the CPU Is the RUN indicator on the Master Unit OF...

Page 13: ...ocedure is explained below CALIBRATION Warm up the module for at least 10 minutes Apply 0 25 50 75 and 100 input signal Check that the A D conversion data for the respective input signal remains withi...

Reviews: