 POLARITY (SW3) 

Table 7

POLARITY SW3-6

Bipolor OFF 

Unipolor ON

When Bipolor is selected, the internal threshold level is 

fixed to 0V.

 EXCITATION SUPPLY (SW3) 

Table 8

EXCITATION SW3-5 

SW3-4

  4V 

ON 

OFF 

 

  8V 

OFF 

ON 

 

12V  ON ON

 PULSE SENSING (SW4) 

*

2

 

Table 9

SENSING SW4-3

Capacitor coupled *

3

 

OFF  

DC coupled *

4

 ON

*2. DIP SW setting is required for PC configuration type.

*3. Frequency range must be 0 – 100 Hz or higher.  0 –

 1 

kHz or higher for sinusoidal waveform input.  Frequencies 

lower than 10 Hz may be out of accuracy conformance.
*4. For sinusoidal waveform input with the pulse ampli

-

tude smaller than 1V p-p, the frequency range must be 0 

– 1 kHz or higher, or extend the sampling time by using 

the PC configurator software.

 NOISE FILTER (SW4) 

*

2

 

Table 10

FILTER SW4-2 SW4-1

Large 

ON 

OFF  

Small 

OFF 

ON  

Without 

OFF 

OFF

Time constant is set to 50 msec. with the ‘large’ noise filter 

setting and to 10 msec. with the ‘small’ noise filter setting.

 OUTPUT TYPE (SW3 & 1) 

Table 11

OUTPUT 

SW3-3 SW3-2 SW1-4 SW1-3 SW1-2 SW1-1

– 

20mA 

OFF ON OFF ON OFF OFF 

-2.5 – +2.5V 

ON  OFF  ON  OFF  OFF  ON 

-10 – +10V 

OFF  OFF  ON  OFF  ON  OFF

 OUTPUT TYPE / PC CONFIG (SW1) 

*

2

 

Table 12

OUTPUT 

SW1-4 SW1-3 SW1-2 SW1-1

0 – 20mA 

OFF 

ON 

OFF 

OFF 

-2.5 – +2.5V 

ON 

OFF 

OFF 

ON 

-10 – +10V 

ON 

OFF 

ON 

OFF

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  DIP SW setting:  Check that the switches are set to ap

-

propriate positions.

3)  Power input voltage:  Check voltage across the terminal 

10 – 12 (AC) or 11 – 12 (DC) with a multimeter.

4)  Input:  Check that the input signal is within 0 – 100% of 

full-scale.

5)  Output:    Check  that  the  load  resistance  meets  the  de

-

scribed specifications.

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%,  75%  and  100%  input  signal.    Check  that  the  output 

signal for the respective input signal remains within accu-

racy described in the data sheet.  When the output is out of 

tolerance, recalibrate the unit using the PC Configurator 
Software (model: M3LPACFG).

Summary of Contents for M3LPA2

Page 1: ...unted inside a panel Insert noise filters for the power source connected to the unit Densei Lambda Model MBS 1220 22 or equivalent is recommended The actual installation environments such as panel con...

Page 2: ...insert a mi nus driver between the euro type connector terminal block and the housing body pull up the driver and pull out the euro type connector terminal block INSTALLATION DIN RAIL MOUNTING Set th...

Page 3: ...NPUT External DC Supply DC POWERED TYPE 2 Be aware that the AC power and DC power connect to different terminals 2 DC POWER INPUT 1 U V 1 3 2 6 5 4 CONFIGURATOR JACK 7 8 10 12 OUTPUT AC POWERED TYPE 2...

Page 4: ...d the pulse sensing type and noise filter must be selected with the DIP SW4 1 through SW4 3 See Tables 9 and 10 For detailed information on the PC configuration refer to the M3LPACFG instruction manua...

Page 5: ...h the large noise filter setting and to 10 msec with the small noise filter setting OUTPUT TYPE SW3 1 Table 11 OUTPUT SW3 3 SW3 2 SW1 4 SW1 3 SW1 2 SW1 1 0 20mA OFF ON OFF ON OFF OFF 2 5 2 5V ON OFF O...

Page 6: ...ght is ON and the LD2 red light is blinking 5 0 Input Ranging Apply the desired minimum input level e g 10 Hz from the simulator and push DOWN button until the LD1 flashes for approx 5 sec and then tu...

Page 7: ...A the green LED is blinking For the model M3LPA2 x B the green LED turns on In order to change the threshold apply simulated 100 input signal and push UP increase or DOWN decrease buttons until the ou...

Page 8: ...explained below Both zero and span are adjustable within 15 1 Run Mode Confirm that the green LED is blinking model M3LPA2 x A or the green LED turns on model M3LPA2 x B 2 Fine Zero Calibration Mode...

Page 9: ...VITY SCALE 50 100V p p 1 20 25 50V p p 1 10 10 25V p p 1 5 5 10V p p 1 2 1 5V p p 1 0 5 1V p p 1 0 1 0 5V p p 1 A specific sensitivity scale is applied according to the pulse amplitude by setting up t...

Page 10: ...operating conditions DIP SW Configuration RUN Mode The transmitter is configured via DIP SW and is in normal operating conditions Output Saturated in PC Configuration Mode Option A The output is satur...

Reviews: