![background image](http://html1.mh-extra.com/html/m-system/m3lpa2/m3lpa2_instruction-manual_3216503004.webp)
M3LPA2
P. 4 / 10
EM-2657 Rev.3
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
When you program the transmitter module, two configura
-
tion modes are available: Field Configuration using DIP SW
/ control buttons, and PC Software. (The Option B type is
for the field configuration only.)
The internal DIP switches are used to configure input and
output type. Once the module is configured, precise ranges
are set up with the front control buttons using a simula-
tor connected to the input terminals and a multimeter con-
nected to the output terminals as a reference.
The calibrated input and output ranges are stored in the in-
ternal memory. The module reads the DIP-switch-calibrat
-
ed configuration only once after the power supply is turned
on. Set the switches with the power supply removed.
■
DIP SW CONFIGURATION MODE
Turn the SW3-8 OFF to enable the DIP SW (Field Configu
-
ration) mode as shown in Table 1.
See Table 3 through 10 to configure the input and Table 11
for the output.
■
PC CONFIGURATION MODE
Turn the SW3-8 ON to enable the PC Configuration mode
as shown in Table 1. All programmable features can be set
up on a PC regardless of other DIP SW setting except for
the following: the output type must be selected with the DIP
SW1-1 through SW1-4 (See Table 12), and the pulse sensing
type and noise filter must be selected with the DIP SW4-1
through SW4-3 (See Tables 9 and 10).
For detailed information on the PC configuration, refer to
the M3LPACFG instruction manual.
EXTERNAL & INTERNAL VIEWS
CONFIGURATION MODE & DIP SW SETTINGS
Configuration DIP SW
10 11 12
7
8
9
4
5
6
1
2
3
Configurator Jack
DOWN Button
UP Button
MODE Button
LED3 (LD3)
LED2 (LD2)
LED1 (LD1)
8
SW3
SW2
SW1
7 6 5 4 3 2 1
ON
OFF
ON
OFF
4 3 2 1
ON
OFF
4 3 2 1
SW4
■
FRONT VIEW
■
SIDE VIEW
■
CONFIGURATION MODE (SW3)
Table 1
MODE SW3-8
DIP SW
OFF
Configuration mode can be
PC ON
Confirmed with the front LED.
■
FRONT CONTROL BUTTON LOCK (SW3)
Table 2
LOCK SW3-1
PC Configuration is not disabled
Unlock OFF
when the front control button
Lock ON
function is locked.
■
INPUT TYPE (SW2)
Table 3
INPUT
SW2-2 SW2-1
Open collector
OFF
OFF
Mechanical contact
Voltage pulse
ON
OFF
Two-wire current pulse
OFF
ON
RS-422 line driver pulse
ON
ON
■
FREQUENCY RANGE (SW2)
Table 4
FREQUENCY
SW2-5 SW2-4 SW2-3
0 – 10 Hz
ON
OFF
OFF
0 – 100 Hz
OFF
ON
OFF
0 – 1k Hz
ON
ON
OFF
0 – 10 kHz
OFF
OFF
ON
0 – 200 kHz
ON
OFF
ON
■
PULSE AMPLITUDE (SW2)
Table 5
AMPLITUDE
MAXIMUM VOLTAGE SW2-8 SW2-7 SW2-6
50 – 100V p-p
100V *
1
OFF OFF OFF
25 – 50V p-p
50V *
2
ON OFF OFF
10 – 25V p-p
25V
OFF ON OFF
5 – 10V p-p
10V
ON
ON OFF
1 – 5V p-p
5V
OFF OFF ON
0.5 – 1V p-p
1V
ON OFF ON
0.1 – 0.5V p-p
0.5V
OFF ON
ON
*1. Max. 30V rms, 42.4V peak or 60V DC for UL approval
*2. Max. 30V rms, 42.4V peak or 50V DC for UL approval
■
CUTOUT (SW3)
Table 6
SW3-7 is usable only with the M3LPA2-x/B.
CUTOUT SW3-7
With (0.1% fixed)
ON
Without
OFF