ADJUSTING DETECTING LEVEL BY USING PC CONFIGURATOR SOFTWARE

PC Configurator Software (model: M3LPACFG) can be used to adjust the detecting level with Option /A type.  Appropriate 

detecting level is determined according to the flow chart below (voltage pulse or 2-wire current pulse input only).

START

Confirm the Sensitivity Scale in Table 14 

below.

Assign the value in the following equation.

Detecting Level (V)*

1

 = 

       DC Offset (V)*

2

 ¥ Sensitivity Scale 

Set DIP SW to the DC coupling and adjust 

the detecting level to the value calculated 

above.

Set to 4V when the calculation result is 

higher than 4V, set to -2V when it is lower 

than -2V.

Set DIP SW to the capacitor 

coupling and adjust the 

detecting level to 0V.

DC coupled input sensing?

No

Yes

*1.

*2.

Rounded off to one decimal place.

Divide a current input (mA) by 10 and convert it into voltage (V).

e.g. Offset = 10mA --> 10mA x 1/10 = 1V

Table 15

 

PULSE AMPLITUDE 

SENSITIVITY SCALE

 

50 – 100V p-p 

  1/20 

 

 

25 – 50V p-p 

  1/10 

 

 

10 – 25V p-p 

  1/5 

 

 

5 – 10V p-p 

  1/2

 

1 – 5V p-p 

1  

 

 

0.5 – 1V p-p 

1  

 

 

0.1 – 0.5V p-p 

1

A specific sensitivity scale is applied according to the pulse 

amplitude by setting up the DIP switch and PC Configura

-

tion Software.  The scaled input voltage is then compared to 

the detecting level at -2.00 t4.00V.
With DC coupling, the scaled maximum input voltage level 

voltage must be higher  than and the scaled minimum input 
voltage level must be lower than the detecting level so that 
the pulse state is accurately detected.

• Setting Examples

Voltage Input (DC Offset = Pulse Amplitude / 2)
 

PULSE 

AMPLITUDE 

DETECTING  

  AMPLITUDE (Vp-p) 

RANGE (Vp-p) 

LEVEL (V)

 

100 

50 – 100 

2.5 

 

 

50 

25 – 50 

2.5 

 

 

30 

25 – 50 

1.5

 

25 

10 – 25 

2.5 

 

 

15 

10 – 25 

1.5 

 

 

10 

5 – 10 

2.5

 

7.5 

5 – 10 

1.9 

 

 

1 – 5 

2.5 

 

 

3.5 

1 – 5 

1.8

 

1 – 5 

 

 

0.5 – 1 

0.5 

 

 

0.5 

0.1 – 0.5 

0.3

Current Input (DC Offset = Pulse Amplitude / 2)
 

PULSE 

AMPLITUDE 

DETECTING  

 AMPLITUDE (mAp-p) 

RANGE (Vp-p) 

LEVEL (V)

 16 (1.6Vp-p) 

1 – 5 

0.8 

 

 25 (2.5Vp-p) 

1 – 5 

1.3

HOW TO RESET TO DEFAULT STATUS

1) Set SW3-4 and SW3-5 to OFF position.
2) Turn on the power supply to the transmitter while pressing MODE button.
3) Wait until green light turns on at the LD1, LD2 and LD3.
4) Reset SW3-4 and SW3-5 to the previous position. Turn off and on the power supply.

Summary of Contents for M3LPA2

Page 1: ...unted inside a panel Insert noise filters for the power source connected to the unit Densei Lambda Model MBS 1220 22 or equivalent is recommended The actual installation environments such as panel con...

Page 2: ...insert a mi nus driver between the euro type connector terminal block and the housing body pull up the driver and pull out the euro type connector terminal block INSTALLATION DIN RAIL MOUNTING Set th...

Page 3: ...NPUT External DC Supply DC POWERED TYPE 2 Be aware that the AC power and DC power connect to different terminals 2 DC POWER INPUT 1 U V 1 3 2 6 5 4 CONFIGURATOR JACK 7 8 10 12 OUTPUT AC POWERED TYPE 2...

Page 4: ...d the pulse sensing type and noise filter must be selected with the DIP SW4 1 through SW4 3 See Tables 9 and 10 For detailed information on the PC configuration refer to the M3LPACFG instruction manua...

Page 5: ...h the large noise filter setting and to 10 msec with the small noise filter setting OUTPUT TYPE SW3 1 Table 11 OUTPUT SW3 3 SW3 2 SW1 4 SW1 3 SW1 2 SW1 1 0 20mA OFF ON OFF ON OFF OFF 2 5 2 5V ON OFF O...

Page 6: ...ght is ON and the LD2 red light is blinking 5 0 Input Ranging Apply the desired minimum input level e g 10 Hz from the simulator and push DOWN button until the LD1 flashes for approx 5 sec and then tu...

Page 7: ...A the green LED is blinking For the model M3LPA2 x B the green LED turns on In order to change the threshold apply simulated 100 input signal and push UP increase or DOWN decrease buttons until the ou...

Page 8: ...explained below Both zero and span are adjustable within 15 1 Run Mode Confirm that the green LED is blinking model M3LPA2 x A or the green LED turns on model M3LPA2 x B 2 Fine Zero Calibration Mode...

Page 9: ...VITY SCALE 50 100V p p 1 20 25 50V p p 1 10 10 25V p p 1 5 5 10V p p 1 2 1 5V p p 1 0 5 1V p p 1 0 1 0 5V p p 1 A specific sensitivity scale is applied according to the pulse amplitude by setting up t...

Page 10: ...operating conditions DIP SW Configuration RUN Mode The transmitter is configured via DIP SW and is in normal operating conditions Output Saturated in PC Configuration Mode Option A The output is satur...

Reviews: