![Lütze LION Series Operating Instructions Manual Download Page 75](http://html1.mh-extra.com/html/lutze/lion-series/lion-series_operating-instructions-manual_1951222075.webp)
LION I/O Modules
▪
Analog Inputs, SIL0
75
10.6.2
Module Function
If certain events are occuring the module 803304 AI4, PT1000, behaves as
follows:
Event
Modul Status
Description
Internal
Hardware
Error
Limited run
▪ The diagnosis bit is set for the affected
channel
▪ The channel will be set to 0x0000.
Limit Error
RUN
▪ The diagnosis bit is set for the affected
channel
▪ The channel will be set regarding the
limit value (minium or maximum
value).