LION I/O Modules
▪
Installation
31
6.6
Wiring the Modules
All modules have terminals with Push-In technology. The terminals are printed
with white pin numbers, starting with 1.
Via terminals, the sensors and actuators of the modules will be connected. It is
possible to connect the modules with pre-assembled cables.
Technical Data – Push-In Terminal
Contact spacing (CS)
5.8 mm
Nominal current
12 A
Color
black
Conductor Size
0.2 – 2.5 mm2 / AWG min 24, max 12
Stripping Length
10 mm
Protection
against incorrect insertion
▪ More information can be found in each chapter of the module.
▪ The maximum length of the cable on each input and output is 50 m
(unshielded), regarding the EMC directive.
▪ Even if the terminal is not used for wiring, the terminal has to be plugged in
to reach IP20.
For wiring the modules, a 3.5×0.6 mm screwdriver is mandatory.
1. Push the orange slots down with a
slotted screwdriver 3.5×0.6 mm.
2. While pushing the slots down, put
the wires in the regarding pin holes.
Each pin hole has its own orange
slot.
3. Release the screw driver.
Fig. 24: Wiring