Digital I/O Modules
▪
Relay Outputs
73
13.3.3
Technical Data
Output Relay Module
Number
6
Data Width in the Process Image
1 Byte Outputs
Current Consumption
at DC 24 V
at DC 16,8 V
nom. 90 mA
130 mA
Potential Insulation
Voltage Insulation
▪
AC 1.5 kV outputs and electronic
▪
AC 1.5 kV channel against
channel
Switch-On Delay
(with CAN processing)
13...28 ms
Switch-Off Delay
(with CAN processing)
11...15 ms
Output Current
▪
DC 0.4 A at DC 150 V
Ohm resistive Load
▪
DC 6 A at DC 30 V
Ohm resistive Load
▪
AC 6 A at AC 250 V
Ohm resistive Load
▪
6 A per relay contact, 20 A for all
contacts
Safety Function
inverse-polarity protection, short-
circuit proof, abnormal temperature
protection
Channel Type
Changer
Module Status Flag
The module status flag remains “0“.
(“0“= no hardware error)
External Fuse
B2 to B6
Summary of Contents for 746400
Page 1: ...Operation Instructions DIOLINE20 Digital I O Modules Version 4 50...
Page 30: ...Digital I O Modules Digital Inputs 26 10 2 5 2 Block Diagram 2x8 Digital Inputs 72 V...
Page 31: ...Digital I O Modules Digital Inputs 27 10 2 5 3 Block Diagram 2x8 Digital Inputs 110 V...
Page 39: ...Digital I O Modules Digital Inputs 35 10 3 5 2 Block Diagram 4x4 Digital Inputs 72 V...
Page 80: ...Digital I O Modules Relay Outputs 76 13 3 5 Operation 13 3 5 1 Block Diagram Relay Outputs...
Page 81: ...77 14 Spacer 14 1 Characteristics Spacer for project planning Does not have any cage clamps...