Digital I/O Modules
▪
Digital Outputs
47
11.3.3
Technical Data
Outputs 24 V Module
Number
8
Data width in the process image
1 Byte Output
2 Byte Input
Byte 1 = Read-back outputs
Byte 2 = Status of the output driver
Current Consumption DC 24 V
nom. 10 mA
Potential Insulation
Voltage Insulation
▪
AC 1.5 kV outputs and electronic
▪
AC 1.0 kV between the output
groups
Output Current
▪
max. 3 A per channel
▪
max. 4 A per potential group
▪
max. 16 A per module
At a max load of 4 A on at least one
channel following fragmentation
results:
(max. 12 A per module):
Output:
1 2 3 4 5 6 7 8
Max load:
0A 2A 4A 0A 0A 4A 2A 0A
Safety Function
inverse-polarity protection, short-
circuit proof, abnormal temperature
protection
Channel Type
N-MOS FET
Standby Current
max. 5 mA per group
Module Status Flag
Error status of the output driver is
entered in the status byte (a bit for
reach output). The module status
flag remains “0“.
(“0“ = no hardware error)
Recommended Error Reaction
Turn off the affected output, and
check the periphery connection
External Fuse
B6
Summary of Contents for 746400
Page 1: ...Operation Instructions DIOLINE20 Digital I O Modules Version 4 50...
Page 30: ...Digital I O Modules Digital Inputs 26 10 2 5 2 Block Diagram 2x8 Digital Inputs 72 V...
Page 31: ...Digital I O Modules Digital Inputs 27 10 2 5 3 Block Diagram 2x8 Digital Inputs 110 V...
Page 39: ...Digital I O Modules Digital Inputs 35 10 3 5 2 Block Diagram 4x4 Digital Inputs 72 V...
Page 80: ...Digital I O Modules Relay Outputs 76 13 3 5 Operation 13 3 5 1 Block Diagram Relay Outputs...
Page 81: ...77 14 Spacer 14 1 Characteristics Spacer for project planning Does not have any cage clamps...
Page 89: ...by L tze Transportation GmbH Weinstadt Germany Technical changes reserved...