Digital I/O Modules
▪
Digital Outputs
57
All outputs have a redundance diode.
Output 110 V Module
redundancy capable
Number
6 redundancy capable
Data Width in the Process Image
1 Byte Outputs
2 Byte Inputs
Byte 1 = Read-back outputs
Byte 2 = Status of the output driver
Current Consumption at DC 24 V
nom. 125 mA
Potential Insulation
Potential Voltage
▪
AC 1.5 kV outputs and
electronic
▪
AC 1.5 kV between the output
groups
Output Current
▪
0.6 A per channel
Safety Function
inverse-polarity protection,
short-circuit proof, abnormal
temperature protection
Channel Type
N-MOS FET
Module Status Flag
Error status of the output driver is
entered in the status byte (one bit for
each output). The module status flag
remains “0“.
(“0“ = no hardware error)
Recommended Error Reaction
Turn off the affected output and
check the periphery connections.
External Fuse
B6