Digital I/O Modules
▪
Digital Inputs
30
10.3.3
Technical Data
Inputs 24 V Module
Number
16
Data Width in the Process Image
2 Byte Inputs
Current Consumption at 24 V DC
nom. 10 mA
Potential Insulation
Insulation Voltage
▪
AC 1.5 kV inputs and
electronic
▪
AC 1.5 kV between potential A,
B, C and D
Input Voltage
“0“ Signal:
▪
DC 0...6 V
“1“ Signal:
▪
DC 12.5...30 V
Input Current
“0“ Signal:
▪
0 mA
1 Signal at DC 24 V:
▪
min 25 mA for 7 ms when
powering up,
sloping to min. 4 mA
“1“ Signal Threshold:
▪
max. 50 mA at DC 30 V
inrush current, min 2 mA at
DC 16.8 V constant current
Limit Threshold (thermic)
10 Hz at 50 % ED
Module Status Flag
The module status flag remains “0“.
(“0“ = no hardware error)
Summary of Contents for 746400
Page 1: ...Operation Instructions DIOLINE20 Digital I O Modules Version 4 50...
Page 30: ...Digital I O Modules Digital Inputs 26 10 2 5 2 Block Diagram 2x8 Digital Inputs 72 V...
Page 31: ...Digital I O Modules Digital Inputs 27 10 2 5 3 Block Diagram 2x8 Digital Inputs 110 V...
Page 39: ...Digital I O Modules Digital Inputs 35 10 3 5 2 Block Diagram 4x4 Digital Inputs 72 V...
Page 80: ...Digital I O Modules Relay Outputs 76 13 3 5 Operation 13 3 5 1 Block Diagram Relay Outputs...
Page 81: ...77 14 Spacer 14 1 Characteristics Spacer for project planning Does not have any cage clamps...
Page 89: ...by L tze Transportation GmbH Weinstadt Germany Technical changes reserved...