Battery Racks, continued
24V Systems
Table 2-B: Battery Rack Dimensions (24V)
L x W x Maximum Installed Height (Inches)
Config.
# Cells
UBC Zone 0
Standard Rack
UBC Zones 1-2B
UBC Zones 3-4
2T/1R
(S-S)
12
(6/tier)
72 x 24.06 x 69.95
72 x 24.06 x 69.95
72 x 24.06 x 69.95
2T/1R
(E-E)
12
(6/tier)
90 x 18.38 x 70.26
90 x 20.63 x 70.26
90 x 20.63 x 70.26
Config.
# Cells
Bellcore Zone 3
Bellcore Zone 4
Pac Bell Zone 4
2T/1R
(S-S)
12
(6/tier)
70.88 x 24.13 x 69.95
70.88 x 24.13 x 69.95
80.47 x 26.85 x 68.88
2T/1R
(E-E)
12
(6/tier)
90 x 20.63 x 70.26
90 x 20.63 x 70.26
98.3 x 23.35 x 69.19