Lucent Technologies Victory Class Batteries WP-93936
Issue 1 May 2000
Installation 6 - 9
Cell Installation Guidelines, continued
Unpacking and
Handling
Large single cells and multi-cell monoblocs are packed in individual
cartons strapped to a wooden pallet. Remove the straps and carefully
lift off cartons for access to lifting slots in the bottom support piece.
Always lift cells from the bottom, never by the posts. A lifting sling and
spreader board are packed in the accessories carton. Slip the lifting
sling under the cell, then install the spreader block on top of the cell.
Ensure that the sling fits in notches in the spreader board. Use the loops
in the sling to hoist the cell.
At the first opportunity, check the electrolyte level in each cell. It
should be between the “high” and “low” level lines on the container. If
the level is more than 1/2-inch below the top of the plates, order a new
cell and file a claim for concealed damage against the carrier. If the cell
plates are covered but the level is lower than one-half-inch below the
“high” level mark, make no additions (i.e., water or acid) until the cells
have been on float charge for one week, and contact Lucent
Technologies Technical Support.
If electrolyte is found on the top of the cell or terminal posts, clean
immediately with a solution consisting of one pound baking soda to one
gallon of water. Do not allow cleaning solution to enter cell.