Lucent Technologies Victory Class Batteries WP-93936
10 - 2 Discharge and Power Data
Issue 1 May 2000
Table 10-A: Battery Discharge Amperes Per Cell
Model WP-93936 List 1
Discharge Rate at
77°F (28°C)
(Hours)*
End of Discharge Volts Per Cell
1.75V
1.80V
1.84V
1.86V
1.88V
1.90V
0.5
1008
845
704
630
562
488
1.0
798
698
609
557
494
441
1.5
651
588
525
483
441
399
2.0
551
509
462
436
399
362
2.5
477
452
415
389
357
331
3.0
432
404
368
352
326
299
4.0
358
341
315
294
278
257
5.0
304
289
268
257
242
221
6.0
266
257
242
231
215
205
8.0
210
201
190
181
170
160
10.0
177
169
159
153
142
132
12.0
153
146
138
133
127
118
24.0
86
83
79
75
72
67
Note: The values in this table include inter-cell connector loss. This loss is based on the use
of four lead plated copper straps between each cell:
side-to-side configuration: strap dimension = 1.0" x 12.12" x 0.12", strap resistance 16.034 x 10
-6
Ω
end-to-end configuration: strap dimension = 1.0" x 8.12" x 0.12", strap resistance 10.266 x 10
-6
Ω
*Hours reserve reflect cell performance at electrolyte specific gravity of 1.215±0.005 at 77°F
(25°C)