Lucent Technologies Lineage
®
2000 400A, 60Hz Ferroresonant Rectifier J85503C-3
Issue 10 July 2000
Troubleshooting and Adjustments 7 - 11
Table 7-F: Additional Conditions/Indications on the J85503C-3
Signal/Condition
Indication
BAT, GRD
Nominal 52-volt control battery fused at 1-1/3
amperes and ground should be applied when a
Lucent Technologies controller is not
connected to the rectifier. When a Lucent
Technologies controller is not present, BAT is
a supply to energize the HV, TR, and EQ
relays. The GRD is connected to TRR and can
serve as the discharge GRD for HV, TR, or
RM.
R+, R-
Battery plant regulation voltage, fused at 1-1/3
amperes and regulation ground can be applied
when a Lucent Technologies controller is not
connected to the rectifier. In this situation, R+
and R- are used for external regulation
sensing.
Front panel digital meter always
active
Switch S2.2 on CM set to Closed (1)
Front panel digital meter active
only when rectifier is ON
Switch S2.2 on CM set to Open (0)
Local equalize switch enabled
Switch S2.1 on CM set to Closed (1)
Local equalize switch disabled
Switch S2.1 on CM set to Open (0)
Remote control (RM48, RM24)
enabled
Switch S1 on CM4 set to Auto/Remote
Local control (RM48, RM24)
Switch S1 on CM4 set to Local/Manual