Lucent Technologies Lineage
®
2000 400A, 60Hz Ferroresonant Rectifier J85503C-3
Issue 10 July 2000
Troubleshooting and Adjustments 7 - 7
Power switch off
Rectifier turned off manually
Power switch off or On
Power LED off
Output meter on
Rectifier operating normally; S2.2 of
CM4 has been enabled.
Power switch off or On (Enabled)
Power LED off
LCA LED On
Load share feature is not operating
properly
ACF LED On
All other conditions "don’t care"
AC input to rectifier fails on all three
phases
Power switch on On or Auto (Standard)
Power LED On (Standard)
Rectifier operating normally except not load
sharing
LSF LED On
Load share interconnect bus has a short
circuit.
Load share bus has opened, but rectifier is
otherwise normal.
Notes:
1. S2.2 on CM4 permits the meter to be On or Off with the rectifier turned off.
2. S1 of CM4 must be in “Remote/Auto Control” position if the Power switch is in the Auto
position.
Table 7-B: Front Panel Conditions and Indications
Condition
Indication