Lucent Technologies Lineage
®
2000 400A, 60Hz Ferroresonant Rectifier J85503C-3
3 - 6 Engineering and Ordering
Issue 10 July 2000
Notes
1. The 323D display meter board (CM3) features the following:
• Power On/Off switch
• Power On LED
• PH LED
• FA LED
• RFA LED
• LCA LED
• LSF LED
• ACF LED
• Equalize LED
• Rectifier volts/Rectifier amperes/Plant voltage display
selection switch
• NL/FL test switch
• Float/Equalize switch
• Output adjust potentiometer
• Equalize potentiometer
• Pin jacks for external meter
2. Adding the 330C Auxiliary Interface Board (CM4) to a 323D
Digital Meter Board provides these additional features:
• The digital meter can be set to display either the output current
or the plant voltage.
• The 330C monitors CFA/RFA, RFA, CB, LOA, EQA and
MAN conditions. It also provides access to RM24, RM48, R+,
R-, RS, RSR, TR, TRR, BAT, GND, HV, EQL, and EQLR.
• Switches on the 330C enable or disable remote control
capability, maintain the meter indication while the unit is off,
and enables or disable the front panel equalize switch.
• The power ON/AUTO/OFF switch enables or disables the
remote control feature.
3. The standard output filter provided with Lists 1, 2, 3, and 4 meets
Bell standard TR-EOP-000151 Issue 1 for output noise levels up
to 44 dBrnc. The optional output filter (List GTS 8336 Issue 2 for
output noise levels of 32 dBrnc for an on-battery condition only
when measured at the battery position.