Lucent Technologies Lineage
®
2000 ECS/GPS Battery Plant J85500G-2
2 - 2 Product Description
Issue 6 May 1999
Altitude
-200 to 13000 feet (-61 to 3962 meters)
For altitudes of 5000 to 13,000 feet, derate maximum
temperature by 3.6 degrees Fahrenheit per 1000 feet above
5000 feet.
For altitudes of 1524 to 3962 meters, derate maximum
temperature by 0.656 degrees Celsius per 100 feet above 1524
meters.
Framework
Type: 7 foot Central Office Framework (standard 26 inch
width)
Vertical mounting centers: 1.00 inches (25 mm)
Horizontal mounting centers: 24.32 inches (618 mm)
Dimensions
Height: 84 inches (2134 mm)
Width: 26 inches (660 mm)
Depth: 18.5 inches (470 mm)
Weight
Initial bay (includes 12 rectifiers): 600 pounds (272 kilograms)
Supplementary Bay (includes 6 rectifiers): 350 pounds (159
kilograms)
Battery Supplementary Bay:
Equipped with 1 string VR batteries: 2100 pounds (953
kilograms)
Equipped with 2 strings VR batteries: 4100 pounds (1860
kilograms)
Earthquake
Initial bay: Zone 4, upper floors
Bays equipped with VR batteries: See Earthquake Bracing,
Section 3
Heat Dissipation
Full load: 5750 watts (19,602 BTU/hr)(Note 1)
Half load: 2888 watts (9845 BTU/hr)
Rectifier, full load: 475 watts (1619 BTU/hr)
ECS Controller, basic and options: 26 watts (89 BTU/hr)
Galaxy, with options: 100 watts
Humidity rating
10% to 95% noncondensing
Audible noise
65 dBa (Note 2)
Electrostatic
discharge
IEC 801-2 Level 5 (15 KV) at 40% relative humidity
Electromagnetic
immunity
10V/m over the range of 20 to 2000MHz
Note 1: Specified at 54 volts dc, 600 amperes output, and nominal input voltages and
frequencies.
Note 2: Measured at 2 feet (6 meters) from the rectifiers installed in plant (six
rectifiers in initial bay).
Table 2-A: Lineage
®
2000 Battery Plant Specifications (Model
J85500G-2)