Lucent Technologies Lineage
®
2000 ECS/GPS Battery Plant J85500G-2
Issue 6 May 1999
Installation 4 - 9
•
Wire AC
•
Set up
•
Plug in
•
Test
Note:
AC wiring should be completed during the initial installation
for all rectifier positions that may be used in the future. If ac
is prewired in this way, growth in rectifier capacity is as
simple as plugging in an additional rectifier. It will also be
possible to add a rectifier without shutting down adjacent
rectifiers to gain access to space for additional ac wiring.
Before proceeding, verify that all rectifier output circuit breakers
are in the OFF position.
Load wiring
For the initial bay, open the dc distribution cover panel by
turning the two 1/4 turn fasteners located on the front of the
panel.
DANGER:
Verify that no voltage is present on the dc distribution bus
bars and that all dc circuit breakers are off before
connecting any load leads.
Run paired leads (supply and return) to each load from a dc
distribution circuit breaker or fuse and from the discharge return
bus. The load supply leads are terminated at the breaker and fuse
panels (directly to the breaker or fuse terminal end). The load
return leads are terminated at the battery plant end on the
discharge return bus, located at the top front of the bus bar
arrangement.
For the supplementary bay, terminate the charge feeder cable to
the initial bay charge bus bar. As in the initial bay, run load
supply cable from the breaker and fuse panels and load return
leads to the discharge return bus in the initial bay.
Recommendations for routing and dressing of load leads as they
leave the battery plant and enter the cable rack system are shown
on the plant assembly drawing, J85500G-2 or in Figure 3-4.
Consult the job application drawings for the routing of these
leads to the load equipment.