Lucent Technologies Lineage
®
2000 ECS/GPS Battery Plant J85500G-2
5 - 6 Maintenance
Issue 6 May 1999
4. Unbolt and remove contactor.
5. Reconnect quick connect leads to new contactor and then
mount new contactor using hardware from Step 4.
6. Plug P501 into J501 on LVD/Fuse board (CP5) and verify
that contactor closes.
7. Replace rectifier and turn on.
8. Close LVD/fuse panel door and verify that LVD FAIL and
LVD OPEN lights are not lit.
LVD/Fuse Board
(CP5)
Replacement
The following equipment is required:
•
standard screwdriver
Procedure: (Refer to Figure 4-3 and T-82673-31 drawing)
WARNING: Failure to follow procedure could result in
service interruption.
1. Remove control cable from front of rectifiers so rectifiers
will remain on.
2. Strap out low voltage contactor (if equipped) to keep
batteries connected.
3. Open distribution panel.
4. Unplug the following connectors from the LVD/Fuse
Board (CP5). Leave the cables dressed.
J502 from P502
J508 from P508
J506 from P506
J501 from P501
J504 from P504
Wires from TB501
5. Remove the 6 mounting screws.
6. Set jumpers J505.1 and J505.2 on replacement LVD/Fuse
Board (CP5). See J85500G-2 drawing for desired
disconnect voltage.