4 - 16 Installation
Issue 6 May 1999
Note:
Step 12 will cause the LVD/R Contactor to CLOSE.
12. Reconnect the following connectors in order listed below:
•
P502 to J502
•
P506 to J506
•
P501 to J501
•
P504 to J504
13. If you are installing more than one 216A Control Unit use
Cable Assembly 847586815 to interconnect each unit. The
216A Control Units will be daisy-chained from P512 to
P511 up to a maximum of five units. The last unit
connected will need Terminator Plug 847631363 inserted
into P512.
14. Connect the 216A Control Unit Interface Cable Assembly
(847586815) to P510 on the BMD1 LVD/Fuse Board and
dress cable out of the distribution and down to the 216A
Control Unit connecting to P511.
15. Close all doors and ensure all covers are installed properly.
16. Replace F507, F508, F509, F511 and F512 with their
respective fuses into the BMD1 LVD/R Fuse Circuit Pack.
NOTICE F512 HAS ORANGE TAB (2 AMP).
17. Place the WARNING label on the controller face close to
the output display
18. Locate the INFORMATION label approximately as shown
in Figure 4-9 (option 2) to cover the original label. This
INFORMATION label (Comcode 847754835 ) is for
Thermal Slope/Step Compensation Without LVD feature
ONLY.