Lucent Technologies ECS Minicell Battery Plant H569-420
Issue 5 February 1997
Installation Tables 6 - 5
Alarm Leads
Table 6-F: T83260-30 Figure H3 Alarm Lead Designation
Terminal
Block-Pin
Designation
Lead
Meaning
101-8
ABS
Alarm Battery Supply
102-7
ACFE C
AC Fail External; alarm causes closure.
102-8
ACFE R
AC Fail External; return
102-9
ACFE O
AC Fail External; Alarm Causes Open.
102-1
BDE C
Battery On Discharge external; alarm
causes closure.
102-3
BDE O
Battery On Discharge External; alarm
causes open.
102-2
BDE R
Battery On Discharge External; return.
101-1
DG
Discharge Ground
103-7
MNFE C
Fuse Alarm Minor External; alarm causes
closure.
103-8
MNFE R
Fuse Alarm Minor External; return.
103-9
MNFE O
Fuse Alarm Major External; alarm causes
open.
104-10
MJFE C
Fuse Alarm Major External; alarm causes
closure.
104-11
MJFE R
Fuse Alarm Major External; return
104-12
MJFE O
Fuse Alarm Major External; alarm causes
open
102-4
HVE C
High Voltage External; alarm causes
closure
102-5
HVE R
High Voltage External; return.
102-6
HVE O
High Voltage External; alarm causes open.
102-12
LVO
Low Voltage Contactor Open
102-11
LVR
Low Voltage Contactor Return
102-10
LVC
Low Voltage Contactor Closed