Lucent Technologies ECS Minicell Battery Plant H569-420
3 - 12 Engineering and Ordering
Issue 5 February 1997
* Circuit breakers rated between 60 and 100 amperes
require two positions on the distribution panel.
Two-position circuit breakers should only be installed in
the top row (positions 12-21 and 32-41). Distribute 60 to
100 ampere circuit breakers on the panel.
18. Circuit breakers rated between 60 and 100 amperes require
a two-position adapter bus bar. This bus bar is provided
with the 6, 2, and 1/0 AWG lug termination kit. See Table
3-I.
19. Do not exceed 200 amperes loading (List 2 current drain)
per circuit breaker bus bar leg. There are four legs in each
Group 7 or 8. The Group 7 and Group 8 distribution panels
accept a maximum of 600 amperes. Do not exceed 600
amperes.
20. Refer to the table below for plug-in fuse and fuse holder
ordering information. The fuse holder is not provided with
the termination lugs or hardware. Order the required lug
termination kit from Table 3-I for each fuse holder.
21. Use the table below when ordering rectifiers. Each rectifier
shelf accommodates a maximum of three rectifiers.
22. Group A includes CP2 circuit pack (without speech
synthesis), battery backup, and a product manual.
23. Group B includes CP2 circuit pack with voice response
(speech chip), battery backup, and a product manual.
Table 3-M: Fuse Holder and Fuses for Groups 7 and 8
Description
Comcode
Amperage
15900-AT Fuse Holder
406980797
N/A
TPA-5 Fuse
407006329
5
TPA-10 Fuse
407006337
10
TPA-15 Fuse
407006345
15
TPA-20 Fuse
407006352
20
TPA-30 Fuse
407006378
30
Table 3-N: Rectifiers for Groups 4 and 5
Description
Apparatus Code
Comcode
+24V, 100 Ampere Rectifier
364B2
107306599