Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
5 - 20 Installation and Testing
Issue 13 December 2000
Distribution Modules
Introduction
If you are using a plug-in distribution module, refer to the appropriate
paragraph (ES610, ES611, ES613) in this section.
Warning
Installing fuses or circuit breakers not specified for use in these
distribution modules may result in injury to service personnel or
equipment damage.
Installing telecom-type fuses not equipped with safety caps may
result in injury to service personnel.
Fuses can produce sparks. Always wear safety glasses to avoid eye
injury.
Caution
Alarm contacts are not fused within the distribution unit. Therefore,
current limiting protection for these contacts must be provided by
external circuits. Maximum ratings for alarm connections on J2 of the
ES610, ES611, and ES613 are 60Vdc and 0.5A. Exceeding these
maximum ratings could result in fire or damage to the unit.
Note
These modules may not be acceptable for protection of building
wiring as defined by the NEC. Protection for internal wiring or short
interconnecting cables that are not part of the building wiring is
acceptable.