Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
5 - 38 Installation and Testing
Issue 13 December 2000
Adding Rectifiers to a Working Plant
Introduction
Rectifiers and converters may be added with input power applied.
However, the On/Standby switch on the unit added must be in the
Standby position.
Procedure
To install a rectifier in a working plant:
Adding Rectifiers to a Working Plant
Step
Action
1
Verify that the On/Standby switch on the module is in the
Standby position.
2
Begin installation of the rectifier in slot #1, installing rectifiers
left to right. Place the module on the shelf and slide it toward
the backplane until the mounting screw prevents any further
backward motion.
3
Using a 3/16" (5mm) Allen-head wrench, seat the module by
turning the mounting screw clockwise.
4
If required, turn the module On.