Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
6 - 8 Remote Access and Control
Issue 13 December 2000
T1.317 Command Language, continued
Table 6-B: Object-Attribute Pairs – Related Commands
Obj,attr
Description
Sta
Cha
Ope
Type
Range of Values
ps1,des
Power system description
✓
text
Lucent ES648
control unit
ps1,sid
Site ID
✓
✓
text
up to 15 characters
ps1,swv
Software version
✓
text
ES648 software
version
dc1,stt
Plant state
✓
text
FLOAT, BOOST,
PBT
dc1,vdc
Plant voltage
✓
number
dd.dd V
dc1,adc
Plant load current
✓
number
ddd.d A
dc1,ubt*
Plant battery temperature
✓
number
dd C
br1,pbt
Plant battery test state
✓
✓
number
0:pbt not active
1:pbt active
br1,pbte
Plant battery test enable
✓
number
0:disabled 1:enabled
p1,phn
Primary phone number
✓
✓
text
up to 25 characters
a1,phn
Alternate phone number
✓
✓
text
up to 25 characters
gm1,fsp
Rectifier set-point
✓
✓
number
dd.dd
gm1,ros
Rectifier on standby
control
✓
✓
number
0:ros not active
1:ros active
gm1,rose
Rectifier on standby
enable
✓
number
0:disabled 1:enabled
bda1,thr
BD threshold
✓
number
dd.dd (52.0 - 55.0)
bda1,sev
BD is major or none
✓
text
MAJ or NO
bs1,bse
Boost enable
✓
number
0:disabled 1:enabled
sc1,typ
Compensation type
✓
text
NAFTA or EURO
eeq1,stt
External equipment
control state
✓
✓
number
0:open 1:closure
eeq1,alrn
External equipment
alarm state
✓
number
0:no alarm
1:alarm closure
eeq1,inp
External equipment input
✓
number
0:open 1:closure
mp1,ins**
Modem initialization
string
✓
✓
text
up to 25 characters
*Although several thermal probes may be connected to a CPS system, only the highest battery
temperature is displayed. The battery temperature is displayed in degrees Celsius.
**This string of characters is sent by the ES648 control unit to the modem to initialize it into
active service. Up to 25 characters may be entered.
•
cha mpl,ins = “at&fev” – change the modem initialization string to “at&fev”
•
cha mpl,ins = “’’ – change the modem initialization string to the default value “at&fev&c1”