Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
4 - 4 Safety
Issue 13 December 2000
Safety Statements, continued
•
In enclosed equipment cabinets, the CPS mounting framework
must be connected directly to the cabinet ac service ground bus. For
applications in huts, vaults, and central offices, the CPS mounting
framework must be connected to the system integrated ground grid.
•
ES610/ES611/ES613 GMT fuse outputs may not be acceptable for
protection of building wiring as defined by the NEC. Protection for
internal wiring or short interconnecting cables that are not part of
the building wiring is acceptable.
•
Installing fuses or circuit breakers not specified for use in these
distribution modules may result in injury to service personnel or
equipment damage. Use only replacement parts listed in this
manual and on the equipment drawings.
•
The telecom-type (e.g., GMT type) fuses can produce sparks during
interruption or clearing of a fault on a high energy circuit. Use only
fuses provided with safety caps for this type of circuit. Installing
telecom-type fuses not equipped with safety caps may result in
injury to service personnel.
•
While installing batteries, follow all safety precautions outlined in
the appropriate battery product manuals.