I269
I
GB
F
E
02
17
31100110
G
B
4
– Select the sub-menu and press
to show the parameters.
– Each parameter is shown with code, description and programmed setting value.
– To modify the setting of one parameter, select it and then press
.
– If the Advanced level access code has not been entered, it will not be possible to enter editing pages and a access-denied message will be shown.
– If instead, the access rights are validated, then the editing screen will be shown.
– When the editing screen is displayed, the parameter setting can be modified with
and
keys. The screen shows the new setting, the maximum and
minimum values, the factory default setting and a bar graph that shows the setting range.
– Pressing simultaneously
and
, the setting is set to factory default.
– Press
MENU
to go back to the parameter selection. The entered value is stored.
– Press
MENU
again to save all the settings and to quit the setup menu. The multimeter executes a reset and goes back to normal operation.
1 - Parameter code
2 - Parameter description
3 - Present setting value
4 - Selected parameter
1 - Selected parameter
2 - Minimum possible setting
3 - Graph bar of the value-range
4 - New value entered
5 - Maximum possible setting
6 - Previous setting
7 - Factory default setting
PARAMETER TABLE
M01 - GENERAL UoM Default Range
P01.01 CT primary A 5 5-10000
P01.02 CT secondary A 5 5
P01.03 Rated voltage V Aut Aut / 50-500000
P01.04 VT usage OFF OFF-ON
P01.05 VT primary V 100 50-500000
P01.06 VT secondary V 100 50-500
P01.07 Wiring L1-L2-L3-N L1-L2-L3-N
L1-L2-L3
L1-L2-L3-N BAL
L1-L2-L3 BAL
L1-N-L2
BAL = Balanced L1-N
P01.01
- CT primary winding rated current.
P01.02
- CT secondary winding rated current. DMG200 and DMG210 are fixed at 5A only.
P01.03
- Line rated voltage. Leaving at Aut, the multimeter automatically adapts bar-graph full scale.
P01.04
- Set to ON if VT are used. If set to OFF, the following two parameters will be ignored.
P01.05
- VT primary winding rated voltage.
P01.06
- VT secondary winding rated voltage.
P01.07
- Set this parameter according to the used wiring diagram. See wiring diagrams on last pages of the manual.
M02 - UTILITY UoM Default Range
P02.01 Language English English
Italiano
Francais
Espanol
Portoguese
P02.02 Display contrast % 50 0-100
P02.03 High backlight level % 100 10-100
P02.04 Low backlight level % 30 10-50
P02.05 Low backlight delay sec 30 5-600
P02.06 Default page return sec 60 OFF / 10-600
P02.07 Default page VL-L VL-L / VL-N ...
P02.08 Default sub-page INST INST / HI / LO /
AVG / MD /GRAPH
P02.09 Display update time sec 0.5 0.1-5.0
P02.06
- If set to OFF, the display remains always at the page where the user left it. If set to a time delay, after that time, the display page goes back to page set
in P02.07.
P02.07
- Number of the page to which the display returns automatically after time specified by P02.06 has elapsed from the last keystroke.
P02.08
- Sub-page type to which the display returns after P02.06 has elapsed.
P03.01
- If set to OFF, password management is disabled and the access to setup parameters and commands menu is allowed.
P03.02
- With P03.01 enabled, value to be specified to get user access. Refer to Password Access section.
P03.03
- Like P03.02, but referred to advanced access.
M03 - PASSWORD UoM Default Range
P03.01 Enable passwords OFF OFF-ON
P03.02 User level password 1000 0-9999
P03.03 Advanced level password 2000 0-9999