Ambient conditions
Operating temperature -20 to +60°C
Storage temperature -30 to +80°C
Relative humidity <80% (IEC/EN 60068-2-78)
Maximum pollution degree 2
Measurement category III
Overvoltage category 3
Altitude
≤
2000m
Climatic sequence Z/ABDM (IEC/EN 60068-2-61)
Mechanical shock 15g (IEC/EN 60068-2-27)
Vibration 0.7g (IEC/EN 60068-2-6)
Insulation
Rated insulation voltage Ui 690V
Rated impulse withstand voltage Uimp 9.5kV
Power frequency withstand voltage 5.2kV
Auxiliary supply and voltage input connections
Type of terminal Screw (fixed)
Number of terminals 4 for voltage inputs
2 for Aux supply
Conductor cross section (min-max) 0.2-4.0mm
2
(24-12AWG)
Tightening torque 0.8Nm (7lbin)
Current Input and RS485 (DMG210 only) connections
Type of terminal Screw (fixed)
Number of terminals 6 for external CT connection
4 for RS485 connection
Conductor cross section (min-max) 0.2-2.5mm
2
(24-12AWG)
Tightening torque 0.44Nm (4lbin)
Housing
Version 4 module (DIN 43880)
Mounting On 35mm DIN rail (IEC/EN 60715)
or by screw using extractible clips
Material Polyamide RAL7035
Degree of protection IP40 on front,
IP20 terminals
Weight 294g (DMG200); 300g (DMG210)
Certifications and compliance
Certifications obtained cULus, EAC, RCM
UL marking Supply voltage 100-240VAC or 110-250VDC
V input: 600V max
I input: 0.005-6A
for supply/voltage inputs AWG Range: 24-12 stranded or solid
Field Wiring Terminals Tightening Torque: 7-9lbin
Use 60°C/75°C copper (Cu) conductor only.
for current inputs AWG Range: 24-12 stranded or solid
Field Wiring Terminals Tightening Torque: 4lbin
Use 60°C/75°C copper (Cu) conductor only.
Comply with standards IEC/EN 61010-1, IEC/EN 61000-6-2,
IEC/EN 61000-6-4, UL508, CSA C22.2 n°14
TECHNICAL CHARACTERISTICS
Auxiliary supply
Nominal voltage Us 100-240V
110-250V
Rated voltage range 85-264V
93.5-300V
Frequency 45-66Hz
Power consumption/dissipation DMG200: 3.5VA 1.2W
DMG210: 4.5VA 1.7W
Immunity time for microbreakings
≥
50ms
Voltage inputs
Type of input Three phase + neutral
Maximum rated nominal voltage Ue 690V
phase-phase
400V
L-N
UL rating 600V
phase-phase
347V
L-N
Measuring range 20 - 830V
L-L
10 - 480V
L-N
Frequency range 45-66Hz
Method of measuring True RMS value
Method of connection Single-phase, two-phase, three-phase with or without
neutral or balanced three-phase system
Current inputs
Rated current Ie 5A
Measuring range 0.010-6A
Type of input Shunt supplied by an external current transformer
(low voltage). Max. 5A
Measuring method True RMS value
Overload capacity +20% Ie
Overload peak 50A for 1 second
Burden (per phase)
≤
0.6W
RS485 Serial interface (DMG210 only)
Baud-rate Programmable 1200-38400 bps
Insulation 1500V~ toward current inputs
Double insulation toward supply
and voltage inputs.
Accuracy
Measuring conditions temperature 23°C ±2°C
voltage L-N 50-480V
L-L 80-830V
current 0.1-1.2 In
frequency 45-66Hz
Voltage ±0.5% ±0.5 digit
Current ±0.5% ±0.5 digit
Frequency ±0.1% ±0.5 digit
Active energy Class 1 (IEC/EN 62053-21)
Reactive energy Class 2 (IEC/EN 62053-23)
Additional errors
Voltage 0.05%/°K
Current 0.05%/°K
Power 0.05%/°K
GB