P04.01
- Selection of average reading calculation method:
Fixed
= Readings are integrated for the set time. Every time the integration time elapses, the Average value is updated with the result of the last integration.
Shift
= The instantaneous values are integrated for a period f time equal to 1/15th of the set time. Every time this interval elapses, the oldest value is replaced
with the new one just calculated. The average value is updated every 1/15th of the time set, considering a time-sliding window that groups the last 15 calculated
values, with a total length equal to integration time setting.
P04.02
= Average readings integration time, used for active, reactive and apparent power.
P04.03
= Readings integration time, used for currents.
M04 - INTEGRATION UoM Default Range
P04.01 Integration mode Shift Fixed / Shift
P04.02 Power integration time min 15 1-60
P04.03 Current integration time min 15 1-60
P05.01
= If set to OFF, the hour counters are disabled and the hour counter page is not shown.
P05.02
= If set to OFF, the partial hour counter is not incremented. If ON, time is incremented as long as DMG is powered. If set to MEAS, the hour counter is
incremented depending on the condition defined by P05.03, P05.04 and P05.05.
P05.03
= Reference measurement for partial hour counter enabling.
P05.04 - P05.05
- Definition of the activation threshold for partial hour counter.
M05 - HOUR COUNTER UoM Default Range
P05.01 Hour counter enable ON OFF-ON
P05.02 Partial hour counter enable OFF OFF - ON - MEAS
P05.03 Reference measurement OFF OFF - (measurement)
P05.04 Enable threshold 0 -9999 - +9999
P05.05 Multiplier x1 /100 - x10k
P06.01
- Selects the reading to be shown on trend graph page.
P06.02
- Choice between automatic range or fixed range defined by the user.
P06.03
- Full scale range value. The unit of measure is the one defined by the selected reading.
P06.04
- Full scale value multiplier.
M06 - TREND GRAPH UoM Default Range
P06.01 Trend graph measurement kW (tot) VL-L (eq) AVG
AVG kW (tot) AVG
kvar (tot) AVG
kVA (tot) AVG
P06.02 Autorange ON OFF-ON
P06.03 Full scale value 1000 0-1000
P06.04 Full scale multiplier x1 x1 - x1k - x1M
M07 - COMMUNICATION UoM Default Range
P07.01 Serial node address 01 01-255
P07.02 Serial speed bps 9600 1200
2400
4800
9600
19200
38400
P07.03 Data format 8 bit - n 8 bit, no parity
8 bit, odd
8 bit, even
7 bit, odd
7 bit, even
P07.04 Stop bits 1 1-2
P07.05 Protocol Modbus RTU Modbus RTU
Modbus ASCII
Note:
This menu is enabled only for DMG210.
P07.01
- Serial address (node number) for the communication protocol.
P07.02
- Serial communication speed.
P07.03
- Data format. Can be set to 7 bits for ASCII protocol only.
P07.04
- Number of stop bits.
P07.05
- Communication protocol selection.
ENERGY METERS PAGE
– The Energy meters page shows the following meters simultaneously:
• Active energy imported and exported
• Reactive energy imported and exported (inductive / capacitive)
• Apparent energy.
– The main page shows the total meters. By pressing
key, the display moves to sub-page with partial meters (clearable by the user).
– To clear energy meters, it is necessary to access the commands menu.
1 - Total / Partial indication