1 - Unit of measure
2 - Measurement
3 - Title bar
4 - Phase indication
5 - Sub-page indication
TABLE OF DISPLAY PAGES
Selection with
and
Selection with
N° PAGE SUB PAGES
1 PHASE-TO-PHASE VOLTAGES - V(L1-L2), V(L2-L3), V(L3-L1), V(LL)EQ HI LO AV GR
2 PHASE-TO-NEUTRAL VOLTAGES - V(L1-N), V(L2-N), V(L3-N), V(L-N)EQ HI LO AV GR
3 PHASE AND NEUTRAL CURRENTS - I(L1), I(L2), I(L3), I(N) HI LO AV MD GR
4 ACTIVE POWER - P(L1), P(L2), P(L3), P(TOT) HI LO AV MD GR
5 REACTIVE POWER - Q(L1), Q(L2), Q(L3), Q(TOT) HI LO AV MD GR
6 APPARENT POWER - S(L1), S(L2), S(L3), S(TOT) HI LO AV MD GR
7 POWER FACTOR - TPF(L1),TPF(L2),TPF(L3),TPF(EQ) HI LO AV GR
8 FREQUENCY-ASYMMETRY - F, ASY(VLL), ASY(VLN), ASY(I) HI LO AV
9 L-L VOLTAGE HARMONIC DISTORTION - THD-V(L1-L2), THD-V(L2-L3), THD-V(L3-L1) HI LO AV GR
10 L-N VOLTAGE HARMONIC DISTORTION - THD-V(L1),THD-V(L2),THD-V(L3) HI LO AV GR
11 CURRENT HARMONIC DISTORTION - THD-I(L1), THD-I(L2) THD-I(L3) HI LO AV GR
12 ENERGY METERS - kWh+(TOT), kWh-(TOT), kvarh+(TOT), kvarh-(TOT), kVA(TOT) PARTIAL
13 TREND GRAPH
14 HOUR COUNTER - Hr(TOT), Hr(Part)
15 INFO/MODEL-SW/HW/PAR REV-SERIAL No.
16 LOGO
Phase-Phase voltages
IN = Instantaneous value
HI = Highest value
LO = Lowest value
AV = Average value
GR = Graphic bars
Phase-Neutral voltages
IN = Instantaneous value
HI = Highest value
LO = Lowest value
AV = Average value
GR = Graphic bars
Phase-Neutral currents
IN = Instantaneous value
HI = Highest value
LO = Lowest value
AV = Average value
MD = Max demand
(continues)
DISPLAY OF READINGS
– The
and
keys allow to scroll the view pages of readings, one by one. The actual page being viewed is written in the title bar.
– Some of the readings may not be shown, depending on the programming and the wiring of the device (for instance, if programmed-wired for a three-phase
without neutral system, L-N voltage page is not shown).
– For every page, the
key allows to move through several sub-pages (for instance to show the highest/lowest peak for the selected readings).
– The actual sub-page being viewed is indicated in the status bar on the bottom left of the display by one of the following icons:
•
IN = Instantaneous value
- Present instantaneous value of the reading, shown by default, every time the page is changed.
•
HI = Highest peak
- Highest peak of the instantaneous value of the present reading. The HIGH values are stored and kept even when auxiliary power is
removed. They can be cleared using the dedicated command (see commands menu).
•
LO = Lowest peak
- Lowest value of the reading, stored from the time of the DMG power-on. It is reset with the same command used for HI values.
•
AV = Average value
- Time-integrated value of the reading. Allows to show measurements with slow variations. See integration menu in setup chapter.
•
MD = Maximum Demand
- Maximum peak of the integrated value. Stored in non-volatile memory and it is resettable with a dedicated command.
•
GR = Graphic bars
- Shows the measurements with graphic bars form.