Technical Data
Technical Data
Conformity
CE
Low Voltage (2006/95/EC) & EMC
(2004/108/EC) Directives
EN61000-6-2:2005, EN61000-6-4:2007
IEC 60335-2-80:2015 IEC 60335-1:2015
Approvals
UL61800-
5-1
CSA C22.2
No113
Input Voltage Phase
Imbalance
≤
2%
Input Voltage
110-240 VAC
Input Current
4.6 @ 120VAC, 2.5A @ 240VAC
Input Frequency
50-60Hz
Supported Power Systems
TT TN
For central ground systems, operation is
permitted without restrictions.
Humidity
≤
95% Non-condensing
Temperature Range
Transport
-40°C…+70°C
Storage
-40°C…+70°C
Operation
-40°C…+50°C (with speed derating above
+40°C)
Installation Height
0 – 4000
a.m.s.l
(with 5%/1000m current derating above
1000m a.m.s.l)
Earth Leakage Current
<=9 mA to PE
Power Conductor Size
(Cord)
Minimum 16AWG 3 Conductors rated 300VAC, use Cop-
per Conductors only. For permanent connection only.