between the buyer and Logix that this is the buyer’s responsibility. It is the responsibility of the installer to ensure that the
installation is in compliance with all national and local codes. Installation should only be attempted by a licensed electrician
familiar with codes, standards, and proper safety procedures for line-voltage installations.
Caution
Read this Entire Document Prior to Installation and Operation of this Unit.
Warning
Risk of Electrical Shock. Severe injury or death can result from electric shock during contact with line voltage wiring and
equipment. Disconnect and lock-out all power sources during installation and service.
M
OUNTING
L
OCATION
C
ONSIDERATIONS
1. Overall Dimensions - 13.4"W x 13.0"H x 7.1"D
2. Environmental
a. Temperature
i.
Operating Temperature -22°F - +122°F (-30°C - +50°C)
ii.
Protect from direct sunlight which can cause the enclosure to exceed its operating temperature limit.
b. Humidity
i.
Maintain operating and storage relative humidity between 10% and 95%, non-condensing.
c. Mechanical Considerations
i.
The UL-Rated Type 4X enclosure allows mounting in indoor or outdoor locations.
ii.
Mount in a low vibration location.
iii.
Mount in a location providing protection from damage.
iv.
Mount in a location providing easy access for servicing.
v.
Mount in proximity to controlled or monitored equipment to reduce installation costs.
3. Networking Considerations
a. WiFi signal range is diminished by walls, metal objects, etc.
b. Ethernet (CAT5e) network cabling is limited to 328 feet. Longer distances require additional equipment (not
provided) such as a repeater or fiber-optic link.
c. Modbus RTU twisted pair cabling is limited to 4000 feet total.
P
OWER
R
EQUIREMENTS
1. The Agility Controller requires 100VAC – 125VAC, 50/60Hz power and consumes up to a total of 10 Amps (including
controller and controlled devices). The controller itself requires 0.5 Amps leaving 9.5 Amps available for controlled
devices.
2. Do not “tap in” to the Agility Controller to power other equipment or otherwise alter the intended function of the
Agility Controller.
S
ECURITY
C
ONSIDERATIONS
1. Network Security Considerations - Agility is not designed to be connected directly to the public Internet. Rather it
should reside behind a firewall on a private network. Remote access, if any, should be implemented through a secure
VPN connection.
2. The Agility Controller’s WiFi network name and password are field configurable. At a minimum, the WiFi Access Point
password should be changed.