background image

The Agility Controller requires a dedicated 120VAC power circuit.  The Agility Controller contains a 10 amp fuse to protect both itself and any controlled devices.

Each digital output is also individually fused with a 4 amp fuse.  Each digital output is rated for a maximum of 1.5 amps for a combined total of 9.5 amps.

Additionally the analog 24V and Com 2 +24V are protected with a self-resetting polymer fuses rated at 1/10

th

 amp.  When a polymer fuse is exposed to

over-current conditions, power must be removed before the fuse will reset.

Analog Sensor Troubleshooting

The safety message "Sensor Under-Range" indicates at least one sensor is sending an excessively low signal (under the normal operating range) to the Agility

panel.  Typically causes of a low signal are a broken wire or damaged sensor.

The safety message "Sensor Over-Range" indicates at least one sensor is sending an excessively high signal (over the normal operating range) to the Agility

panel.  Typically causes of a over-range signal are a shorted wire or damaged sensor.  A faulty sensor will display a series of question marks instead of a normal

sensor reading.  View I/O Status to ascertain which sensor is faulting.  Moisture penetration into a sensor's enclosure is the most common source of sensor

failure.  Refer to the sensor installation wiring diagrams for installation information.

Problem

Test

Possible Solution

Comments

"Sensor Under-

Range" safety

message.

M24VDC supply at the

sensor.  The voltage should be near

+24VDC.

1. The +24VDC Power wire is shorted to the Common

(shield) wire.  An Automatically Resettable fuse protect

the sensor's +24VDC power.  The cause of the short

must be removed 24VDC power will be

restored.  In some cases, the Agility controller must be

powered-down for approximately 5 seconds.

2. Break in supply wire to sensor.

3. The sensor supply is wired incorrectly.  The sensor

should be supplied by +24VDC power from the "Pwr"

terminal.  Review the wiring diagram and correct any

wiring errors.

4. The A24VDC supply is faulty.  Replace the Agility

controller assembly.

Refer to

the Sensor

Diagnostics

Diagram

"Sensor Under-

Range" safety

message

(continued).

Measure the signal wire from the

sensor.  It should be between

+0.5VDC and +3VDC

(approximately).

1. Sensor is bad if voltage is not b0.5VDC and

+3VDC, often from water damage.  Replace Sensor if

signs of corrosion are present.

2. Signal wire is broken or disconnected if voltage is near

zero.

Refer to

the Sensor

Diagnostics

Diagram

Summary of Contents for AGILITY Series

Page 1: ...e tablet laptop or PC b Built in online help system and documentation 2 Agility Controller Platform a Up to 4 Analog Sensor Inputs for measuring Temperature Pressure Humidity etc b Up to 2 fully isola...

Page 2: ...variety of applications i Up to 6 fans or pumps in any combination ii 1 alarm output for annunciators or alerting systems iii 1 fan fault alarm input b Fans can be a single speed or Variable Speed wit...

Page 3: ...bration location iii Mount in a location providing protection from damage iv Mount in a location providing easy access for servicing v Mount in proximity to controlled or monitored equipment to reduce...

Page 4: ...r equal Limit total network cabling length to 4000 feet QUICK START OVERVIEW 1 Install the Agility Controller following the provided installation instructions and wiring diagrams At a minimum wire the...

Page 5: ...require additional IT support to determine the Agility Controller s IP address obtained from the existing WiFi Access Point 3 Disable WiFi Access The WiFi interface is disabled WIFI NETWORK SETTINGS P...

Page 6: ...sk optional Enter the Broadcast Mask for this device If unknown or not required enter 0 0 0 0 d Eth0 Gateway Enter the Gateway address for this device For example 10 0 100 1 The default Gateway addres...

Page 7: ...c Type Speed i Up to 150Mbps data rate ii IEEE 802 11n g b is compatible with a wide range of WiFi devices 4 Ethernet Network a 10 100 BaseT b TCP IP Protocol...

Page 8: ...you wish to manually adjust the time and or date Daylight Saving Time Beginning Date Daylight Saving Time Ending Date Starting in March of 2007 daylight time in the United States began on the second S...

Page 9: ...onnect to Existing join existing WiFi network or Disable WiFi Access Access Point Channel Enter the WiFi Access Point channel This is only utilized for Local Access Point WiFi networks Typical values...

Page 10: ...uration have your IT department configure this device The Default button forces the network configuration back to the factory configured settings The Agility Controller s MAC Address is shown at the b...

Page 11: ...not entered the page s settings will still be displayed allowing observation but not modification Setup Passwords To access the Setup Passwords page from the Secure Access menu select Setup Passwords...

Page 12: ...tripped on a high pressure condition The Functional output will de energize on loss of control power EPCS malfunction pressure sensor fault or pressure sensor wiring fault EPCS Emergency Stop Digital...

Page 13: ...When the zone pressure exceeds either the Zone Trip Pressure or the fixed setpoint the zone is tripped and the crossover valve is opened Select Zone Type Each EPCS zone must be configured to its vess...

Page 14: ...nimum all circuits both inside the panel and interfaced to the panel be thoroughly verified as disconnected and safe with a high quality electrical meter which is tested to be functional before and af...

Page 15: ...ller has sent a message The RX LED indicates the Agility Controller has received a message The Ethernet jack has a green LED which indicates a basic connection to the network It does not indicate that...

Page 16: ...O Status to ascertain which sensor is faulting Moisture penetration into a sensor s enclosure is the most common source of sensor failure Refer to the sensor installation wiring diagrams for installa...

Page 17: ...hole at the lowest point to limit moisture related problems 3 Sensor is damaged or faulty and needs replacing Analog Sensor Calibration The Sensor Calibration routine permits small adjustments to fine...

Page 18: ...ooting The Agility Controller s two analog outputs generate an active 4 20mA signal to control variable speed or position devices including modulating valves and variable speed motors Since the Agilit...

Page 19: ...ure output voltage with a load connected 1 Connected load is very small less than 25mA and leakage current is causing the output to stay at or near 120VAC 2 Connect a larger load and re measure output...

Page 20: ...is corrupting the Ethernet network For example a newly installed web camera was improperly configured with the same IP address as the Agility Controller resulting in an address conflict The symptoms...

Page 21: ...V CR 2032 CH1 CH2 24VAC Power COM 2 COM 1 V Com Data Data Com Data Data Sig1 Ret1 Sig2 Ret2 Analog Outputs Pwr1 Sig1 Com1 Pwr2 Sig2 Com2 Pwr3 Sig3 Com3 Pwr4 Sig4 Com4 Analog Sensor Inputs 3V Battery D...

Page 22: ...1 C H2 CH1 CH2 CH3 CH4 Analog Configuration Agility Controller VDC 24 0 VDC 1 7 VDC 1 7 24V Power 4 20mA Signal Shi eld Sensor Transmitter Sensor Probe Should be between 23 and 25 VDC About 0 6 VDC 4...

Page 23: ...ission of The Controls Group In c LOGIX is a registered trademark of The Controls Group Inc Drawing Filename Date Rev Drawn by Title 07 11 2016 Agility Digital Input Output Schematic 01 MAG AgilityDig...

Page 24: ...3V CR2032 CH1 CH2 ON 24VAC Power COM 2 COM 1 V Com Data Data Com Data Data Sig1 Ret1 Sig2 Ret2 Analog Outputs Pwr1 Sig1 Com1 Pwr2 Sig2 Com2 Pwr3 Sig3 Com3 Pwr4 Sig4 Com4 Analog Sensor Inputs 3V Batte...

Page 25: ...K Black Or Orange field wiring panel wiring panel terminal block LEGEND R panel screw terminal L2 L2 W 14 L2 L2 P1 P1 NEUTRAL 14 Agility E P C S Wiring Diagram Agility_EPCS_Wiring_Diagram Zone 1 Press...

Reviews: