Page B-6
FPU-32 Feeder Protection Unit
Rev.
2-A-103014
Appendix B, FPU-32 Setup Record
F
UNCTION
& S
ET
P
OINT
M
IN
D
EFAUL
T
M
AX
U
NIT
P
ROGRAM
S
ELECTION
Phase Loss
Trip Action
Disabled
Disabled
Trip2
Trip1
Trip3
Trip Delay
1.00
5.00
100.00
s
Alarm Action
Disabled
Disabled
Alarm2
Alarm1
Alarm3
Alarm Delay
1.00
2.00
100.00
s
Phase Reverse
Trip Action
Disabled
Disabled
Trip2
Trip1
Trip3
Trip Delay
1.00
5.00
100.00
s
Alarm Action
Disabled
Disabled
Alarm2
Alarm1
Alarm3
Alarm Delay
1.00
2.00
100.00
s
PTC Temperature
Trip Action
Disabled
Disabled
Trip2
Trip1
Trip3
Alarm Action
Disabled
Disabled
Alarm2
Alarm1
Alarm3
RTD Temperature
Trip Action
Disabled
Disabled
Trip2
Trip1
Trip3
Trip Level
40.00
200.00
230.00
°C
Alarm Action
Disabled
Disabled
Alarm2
Alarm1
Alarm3
Alarm Level
40.00
130.00
230.00
°C
RTD-Sensor-Error Trip Action
Disabled
Disabled
Trip2
Trip1
Trip3
RTD-Sensor-Error Alarm
Action
Disabled
Disabled
Alarm2
Alarm1
Alarm3
(1)
Locked when current is detected.