Page B-5
FPU-32 Feeder Protection Unit
Rev.
2-A-103014
Appendix B, FPU-32 Setup Record
F
UNCTION
& S
ET
P
OINT
M
IN
D
EFAUL
T
M
AX
U
NIT
P
ROGRAM
S
ELECTION
Earth-Fault 3I
0
Definite Time –
Group1
Trip Action
Disabled
Disabled
Trip2
Trip1
Trip3
Trip Level
0.10
10.00
15.00
x I
p
Trip Delay
0.00
0.05
10.00
s
Alarm Action
Disabled
Disabled
Alarm2
Alarm1
Alarm3
Alarm Level
0.10
10.00
15.00
x I
p
Alarm Delay
0.00
0.05
10.00
s
Earth-Fault 3I
0
Definite Time –
Group2
Trip Action
Disabled
Disabled
Trip2
Trip1
Trip3
Trip Level
0.10
10.00
15.00
x I
p
Trip Delay
0.00
0.05
10.00
s
Alarm Action
Disabled
Disabled
Alarm2
Alarm1
Alarm3
Alarm Level
0.10
10.00
15.00
x I
p
Alarm Delay
0.00
0.05
10.00
s
Earth-Fault CT Input Definite
Time – Group1
Trip Action
Trip1
Disabled
Trip2
Trip1
Trip3
Trip Level
0.01
0.40
1.00
x I
e
Trip Delay
0.00
0.25
100.00
s
Alarm Action
Alarm1
Disabled
Alarm2
Alarm1
Alarm3
Alarm Level
0.01
0.20
1.00
x I
e
Alarm Delay
0.00
1.00
100.00
s
Earth-Fault CT Input Definite
Time – Group2
Trip Action
Trip1
Disabled
Trip2
Trip1
Trip3
Trip Level
0.01
0.40
1.00
x I
e
Trip Delay
0.00
0.25
100.00
s
Alarm Action
Alarm1
Disabled
Alarm2
Alarm1
Alarm3
Alarm Level
0.01
0.20
1.00
x I
e
Alarm Delay
0.00
1.00
100.00
s
Unbalance
Trip Action
Trip1
Disabled
Trip2
Trip1
Trip3
Trip Level
(Per unit based on I
2
/I
1.
)
0.05 0.25 1.00 pu
Trip Delay
1.00
15.00
100.00
s
Alarm Action
Alarm1
Disabled
Alarm2
Alarm1
Alarm3
Alarm Level
(Per unit based on I
2
/I
1.
)
0.05 0.10 1.00 pu
Alarm Delay
1.00
10.00
100.00
s