Page 4-1
FPU-32 Feeder Protection Unit
Rev.
2-A-103014
Operation and Setup
4. O
PERATION
AND
S
ETUP
4.1 D
ISPLAY AND
I
NDICATION
All FPU-32 information displays and settings can be
accessed using the FPU-32 menu system, the TIA-232
interface, or a network-communications interface. Use
SE-COMM-RIS software to program with a personal
computer.
In the following sections, menu items and setup
parameters are listed in italics and are shown in the format
displayed on the alphanumeric LCD. The LCD cannot
display subscripts and superscripts.
Menu selection is in the following format:
Menu
1
|
Sub Menu 1
|
Sub Menu 2
|
Sub Menu 3
|
……
Example:
For the menu item shown in Fig. 4.1, the
notation is
Setup
|
System Ratings
|
CT Primary
Metering
Messages
Setup
Protection
System Ratings
Phase CT
Primary
•
EF-CT-Primary
•
Frequency
•
•
•
FIGURE 4.1 Menu Example.
Fig. 4.2 shows the symbols that assist in navigating the
menu system and how these symbols relate to the arrow
keys on the FPU-32. See the FPU-32 menu map in
Appendix A.
4.1.1 F
RONT-
P
ANEL
LED
I
NDICATION
Menu:
Setup
System Config
UPI LED
The red TRIP and yellow ALARM LED’s indicate a
trip or alarm condition. The green ACTIVE LED is OFF
when current is not detected and is ON when current is
detected. The yellow UPI LED is a user-programmable
indicator and its function is defined by one of the menu
selections shown in Table 4.1.
TABLE 4.1 UPI LED F
UNCTIONS
S
ELECTION
LED O
N
C
ONDITION
None
LED remains off.
Trip1
Trip 1 condition exists.
Trip2
Trip 2 condition exists.
Trip3
Trip 3 condition exists.
Alarm1
Alarm 1 condition exists.
Alarm2
Alarm 2 condition exists.
Alarm3
Alarm 3 condition exists.
Relay1
Relay 1 is energized.
Relay2
Relay 2 is energized.
Relay3
Relay 3 is energized.
Digital Input
Digital input is valid.
Current Detected
Current is above 2% CT-primary
rating.
3I
0
Pickup
3I
0
current exceeds inverse curve
pickup value.
Phase Pickup
Phase current exceeds inverse curve
pickup value.
ETR
FPU-32 is in Emergency Thermal
Reset state.
Network Run1
Run 1 is issued by a network
command.
Net Activity
Activity is detected on the
communications interface.
¬¬¬¬¬ TITLE
„
½ MENU ITEM 1 Ñ
² MENU ITEM 2 ¼
« MENU ITEM 3 *
These symbols indicate the
menu level. Up to five submenu-
level symbols may be displayed.
Use left-arrow key or ESC to
move back one menu level.
Indicates that there are related data
displays to the left or right of this
display. Use left- or right-arrow
keys to view adjacent data displays.
Use right-arrow key to
select submenu.
Use right-arrow key to
display data.
Indicates active item in
list-type set-point
displays.
Cursor indicates selected
menu item and shape
indicates available scrolling
directions.
Indicates top of list. Scroll
using down-arrow key.
Scroll using up- or down-
arrow keys.
Indicates bottom of list.
Scroll using up-arrow key.
FIGURE 4.2 Menu Symbols.